Plan Review Notes
Plan Review Notes For Permit 09110341
Permit Number 09110341
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-11-18 16:14:34*****DENIED*****
  
 1. IT IS INDICATED IN THE FIRE SPRINKLER HEAD SCHEDULE
 OF 16 PENDANT HEADS TO BE RELOCATED, BUT ONLY 12
 SPRINKLERS INDICATED IN THE HYDRAULIC CALCULATIONS
 SUBMITTAL. PLEASE EXPLAIN AND/OR CORRELATE.
  
 2. INDICATE BY CLOUDING (OR SOME OTHER INDICATOR) OF
 THE SPINKLER HEADS WHICH WERE UNDER THIS POJECT SCOPE
 OF WORK.
  
  
 PLEASE BE ADVISED THAT AT LEAST TWO (2) NO MORE THAN
 THREE (3) PLANS SHALL BE SUBMITTED FOR REVIEW. THERE
 WERE 5 SETS THAT WAS SUBMITTED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722