2010-02-23 15:56:39BUILDING PLAN REVIEW
 PERMIT: 09110339
 ADD: 429 BELVEDERE RD- UPPER UNIT
 CONT: TO BE DETERMINED
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 FEB. 11/ 2010
 3RD REVIEW
 ACTION: DENIED
 DESIGN CRITERIA FOR SECOND FLOOR:
 R-3 WITH 40 LB LIVE LOAD/ 10 LB DEAD LOAD FOR FLOOR
 SYSTEM.
  
 1-12) COMPLIED.
  
 13) PROVISO: SEMI-COMPLIED.SHEET A3.1 ALSO INDICATES TO
 HAVE A AIR COMPRESSOR LOCATED WEST OF THE 2 STORY AREA,
 THIS COMPRESSOR WOULD BE LOCATED ON THE FIRST FLOOR
 ROOF REQUIRING A A/C STAND. PRODUCT APPROVALS WERE
 SUBMITTED. THE UPDATED PLANS INDICATE STRAPPING OVER
 THE COMPRESSOR UNIT. THIS IS NOT AN APPROVED METHOD OF
 COMPLYING WITH 301.12 FBC-MECHANICAL/ 2007.
 WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST WIND PRESSURES ON THE EQUIPMENT AND
 THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING.
  
 301.12 FBC MECHANICAL/ 2007
  
 14) COMPLIED.
  
 15) PLANS APPEAR TO BE CODE COMLIANT, MUST BE LEFT IN
 FAILED UNTIL CONTRACTOR LICENSURE IS VERIFIED.
 JIM WITMER C. B. O.