| 2010-02-23 15:56:39 | BUILDING PLAN REVIEW | | | PERMIT: 09110339 | | | ADD: 429 BELVEDERE RD- UPPER UNIT | | | CONT: TO BE DETERMINED | | | TEL: (561)832-1500 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | FEB. 11/ 2010 | | | 3RD REVIEW | | | ACTION: DENIED | | | DESIGN CRITERIA FOR SECOND FLOOR: | | | R-3 WITH 40 LB LIVE LOAD/ 10 LB DEAD LOAD FOR FLOOR | | | SYSTEM. | | | | | | 1-12) COMPLIED. | | | | | | 13) PROVISO: SEMI-COMPLIED.SHEET A3.1 ALSO INDICATES TO | | | HAVE A AIR COMPRESSOR LOCATED WEST OF THE 2 STORY AREA, | | | THIS COMPRESSOR WOULD BE LOCATED ON THE FIRST FLOOR | | | ROOF REQUIRING A A/C STAND. PRODUCT APPROVALS WERE | | | SUBMITTED. THE UPDATED PLANS INDICATE STRAPPING OVER | | | THE COMPRESSOR UNIT. THIS IS NOT AN APPROVED METHOD OF | | | COMPLYING WITH 301.12 FBC-MECHANICAL/ 2007. | | | WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND | | | SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND | | | INSTALLED TO RESIST WIND PRESSURES ON THE EQUIPMENT AND | | | THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 301.12 FBC MECHANICAL/ 2007 | | | | | | 14) COMPLIED. | | | | | | 15) PLANS APPEAR TO BE CODE COMLIANT, MUST BE LEFT IN | | | FAILED UNTIL CONTRACTOR LICENSURE IS VERIFIED. | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | |
|