2010-02-11 11:08:49BUILDING PLAN REVIEW
 PERMIT: 09110339
 ADD: 429 BELVEDERE RD- UPPER UNIT
 CONT: TO BE DETERMINED
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 FEB. 11/ 2010
 3RD REVIEW
 ACTION: DENIED
 DESIGN CRITERIA FOR SECOND FLOOR:
 R-3 WITH 40 LB LIVE LOAD/ 10 LB DEAD LOAD FOR FLOOR
 SYSTEM.
  
 1) COMPLIED.
  
 2) PLEASE COMPARE THE AMOUNT OF WORK IS TO BE COMPLETED
 IN THE SCOPE OF THE PLANS VERSES THE DESCRIPTION OF
 WORK WITHIN THE PLANS. THE PERMIT APPLICATION AND THE
 VALUE OF $3,000.00. PLEASE CORRECT TTHE DESCRIPTION OF
 WORK ON THE PERMIT APPLICATION AND THE VALUE OF THE
 PERMIT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF
 PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3- 12) COMPLIED.
  
 13) PROVISO: SEMI-COMPLIED.SHEET A3.1 ALSO INDICATES TO
 HAVE A AIR COMPRESSOR LOCATED WEST OF THE 2 STORY AREA,
 THIS COMPRESSOR WOULD BE LOCATED ON THE FIRST FLOOR
 ROOF REQUIRING A A/C STAND. PRODUCT APPROVALS WERE
 SUBMITTED. THE UPDATED PLANS INDICATE STRAPPING OVER
 THE COMPRESSOR UNIT. THIS IS NOT AN APPROVED METHOD OF
 COMPLYING WITH 301.12 FBC-MECHANICAL/ 2007.
 WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST WIND PRESSURES ON THE EQUIPMENT AND
 THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING.
 301.13 FBC MECHANICAL./ 2004
 301.12 FBC MECHANICAL/ 2007
  
 14) COMPLIED.
  
 15) ONCE PLANS ARE OK TO ISSUE PLANS WILL NEED TO BE
 LEFT IN FAILED STATIS UNTIL CONTRACTOR LICENSURE CAN BE
 VERIFIED.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  