2010-01-25 11:06:58BUILDING PLAN REVIEW
 PERMIT: 09110339
 ADD: 429 BELVEDERE RD- UPPER UNIT
 CONT: TO BE DETERMINED
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 JAN. 25/ 2010
 2ND REVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) PLEASE COMPARE THE AMOUNT OF WORK IS TO BE COMPLETED
 IN THE SCOPE OF THE PLANS VERSES THE DESCRIPTION OF
 WORK WITHIN THE PLANS. THE PERMIT APPLICATION AND THE
 VALUE OF $3,000.00. PLEASE CORRECT TTHE DESCRIPTION OF
 WORK ON THE PERMIT APPLICATION AND THE VALUE OF THE
 PERMIT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF
 PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) 2ND REQUEST, THE PERMIT APPLICATION AND SHEET 2.1
 INDICATES THE REPAIR OR REPLACEMENT OF 2X10 FLOOR
 JOIST, PLEASE PROVIDE SPECIES, GRADE OF WOOD, THE LIVE
 AND DEAD LOADS TO BE ASSUMED. TABLE 2308.8(1). PROVIDE
 ALLOWABLE DEFLECTION OF THE STRUCTURAL MEMBERS.
  
 4-8) COMPLIED.
  
 9) THE BATH EGRESS WINDOW WILL BE CONSIDERED A
 HAZARDOUS LOCATION. R308.4(5) & (10)PLEASE PROVIDE THE
 WINDOW SILL HEIGHT ABOVE THE TUB OR SHOWER FLOOR. BOTH
 WINDOWS ON THE NORTH END OF THE BUILDING ARE LOCATED
 DIRECTLY ABOVE THE ONLY MEANS OF EGRESS ( STAIRWAY)
 REQUIRING A 1HR SEPERATION 1023.6.
  
 10) 2ND REQUEST, 1609.1.4 PROTECTION OF OPENINGS IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET
 (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST. 2. GLAZED OPENINGS LOCATED MORE
 THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
 FL BLD CODE 1609.6.2.2 / FL ADMINISTRATIVE RULE 9B-72,
 COMPONENTS & CLADDING, PROVIDE 2 COPIES OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 10A) OPERABLE WINDOWS
 10B) MULLIONS PLANS ARE NOT CLEAR AS IF THERE IS A
 FRAMING MEMBER BETWEEN WINDOWS?
 10C) EGRESS DOOR
 10D) STORM SHUTTERS OR PANELS
 10E) PRE-MANUFACTURED A/C STAND. QUESTION # 13.
 10F) ROOFING ASSEMBLIES, IF WORK IS TO BE ACCOMPLISHED
 ON THE ROOF
  
 11) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12)COMPLIED.
  
 13) SHEET A3.1 ALSO INDICATES TO HAVE A AIR COMPRESSOR
 LOCATED WEST OF THE 2 STORY AREA, THIS COMPRESSOR WOULD
 BE LOCATED ON THE FIRST FLOOR ROOF REQUIRING A A/C
 STAND. PRE-MANUFACTURED A/C STANDS WILL REQUIRE PRODUCT
 APPROVALS, FL ADMINISTRATIVE RULE 9B-72 (31)(G).
  
 14) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4. FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4,
 1714.5.1 & EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A
 COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM BAR REINFORCING REQUIREMENTS, WALL PRESSURE
 ZONES, SLAT TYPES, ETC., SHALL BE SUBMITTED AT TIME OF
 PERMIT APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15) ONCE PLANS ARE OK TO ISSUE PLANS WILL NEED TO BE
 LEFT IN FAILED STATIS UNTIL CONTRACTOR LICENSURE CAN BE
 VERIFIED.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  