Plan Review Notes
Plan Review Notes For Permit 09110339
Permit Number 09110339
Review Stop B
Sequence Number 1
Notes
Date Text
2009-11-18 16:19:47BUILDING PLAN REVIEW
 PERMIT: 09110339
 ADD: 429 BELVEDERE RD- UPPER UNIT
 CONT: TO BE DETERMINED
 TEL: (561)832-1500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 NOV.11/ 2009
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS DO NOT PROVIDE WHAT TYPE OF OCCUPANCY IS
 BUILDING IS DECLARING. IT APPEARS TO BE A MIXED USE
 BUILDING AS TO THE DETAIL 6/ 2.1PLEASE DECLARE THE TYPE
 OF OCCUPANCY IS LOCATED ON THE FIRST FLOOR AND SECOND
 FLOOR. THE PROPERTY APPRAISERS LIST THE FIRST FLOOR AS
 A MEDICAL OFFICE AND UNFINISHED OFFICE UPSTAIRS. IS
 THIS A CHANGE OF USE?
 1A) WILL THE UPSTAIRS UNIT BE A DIFFERENT TENANT THAN
 THE FIRST FLOOR, FBC 708.1 WILL REQUIRE A ONE HR
 SEPERATION BETWEEN TENANTSOF THE FIRST FLOOR AND SECOND
 FLOOR TENANT.
  
 1B) IS THE BUILDING FIRE SPRINKLERED? FOR THE PURPOSES
 OF THIS REVIEW WE WILL ASUME NON-SPRIKLERED!
  
 1C) THERE WOULD ALSO BE A OCCUPANCY SEPERATION BETWEEN
 THE FIRST FLOOR OCCUPANCY AND THE SECOND FLOOR. PLEASE
 REVIEW TABLE 508.3 FOR THE REQUIRED HOURLY RATING
 BETWEEN OCCUPANCIES. FOR EXAMPLE IF THE UPSTAIRS IS A
 R3 OCCUPANCY AND THE FIRST FLOOR BEING A BUSINESS
 OCCUPANCY THEN A TWO HOUR FLOOR/CEILING ASSEMBLY WOULD
 BE REQUIRED FOR A NON-SPRINKLERED BUILDING.
  
 2) PLEASE COMPARE THE AMOUNT OF WORK IS TO BE COMPLETED
 IN THE SCOPE OF THE PLANS VERSES THE DESCRIPTION OF
 WORK IN THE PERMIT APPLICATION AND THE VALUE OF
 $3,000.00. PLEASE CORRECT TTHE DESCRIPTION OF WORK ON
 THE PERMIT APPLICATION AND THE VALUE OF THE PERMIT .
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) THE PERMIT APPLICATION AND SHEET 2.1 INDICATES THE
 REPAIR OR REPLACEMENT OF 2X10 FLOOR JOIST, PLEASE
 PROVIDE SPECIES, GRADE OF WOOD, SPACING , SPANS AND THE
 LIVE AND DEAD LOADS TO BE ASSUMED. TABLE 2308.8(1).
 PROVIDE ALLOWABLE DEFLECTION OF THE STRUCTURAL MEMBERS.
  
 4) SHEET 2.1 DOE NOT INDICATE HOW THE EXISTING AND
 REPLACED FLOOR JOIST ARE GOING TO BE ANCHORED AND OR
 SUPPORTED LATERALLY, SECTION 2308.2.
  
 5) SHEET 2.1 INDICATES A NEW 3X8 GLU-LAM BEAM AND NEW
 STEEL COLUMN BUT NO MENTION OF HOW THE GLU-LAM BEAM
 WILL BE SUPPORTED AT BOTH ENDS?
  
 6) WILL THE FLOOR JOIST REQUIRE BRIDGING OR LATERAL
 SUPPORT? SECTION 2308.8.5.
  
 7) SHEET 2.1 THE NEW 4X4 STEEL COLUMN PROVIDES THE
 CONNECTION FOR THE UPPER BRACKET BUT IS MISSING THE
 BOTTOM ANCHOR TYPE AND LENGTH? 106.1.2 ADDITIONAL
 INFORMATION REQUIRED,
  
 8) FOR THE UPSTAIRS OCCUPANCY FOR THE PURPOSES OF THIS
 PLANS REVIEW IT WILL BE ASSUMED TO BE A R3 OCCUPANCY.
 THE PLANS INDICATE THE MAIN ENTRY/ EXIT DOOR TO BE A
 2'-8" DOORWAY PLEASE REVIEW R311.4.1-2. REQUIRING A 36'
 WIDE DOOR.
  
 9) THE BATH EGRESS WINDOW WILL BE CONSIDERED A
 HAZARDOUS LOCATION. R308.4(5) & (10).
  
 10) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 FL BLD CODE 1609.6.2.2 / FL ADMINISTRATIVE RULE 9B-72,
 COMPONENTS & CLADDING, PROVIDE 2 COPIES OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 10A) OPERABLE WINDOWS
 10B) MULLIONS PLANS ARE NOT CLEAR AS IF THERE IS A
 FRAMING MEMBER BETWEEN WINDOWS?
 10C) EGRESS DOOR
 10D) STORM SHUTTERS OR PANELS
 10E) PRE-MANUFACTURED A/C STAND.
 10F) ROOFING ASSEMBLIES, IF WORK IS TO BE ACCOMPLISHED
 ON THE ROOF
  
 11) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12) PLEASE PROVIDE ADDITIONAL INFORMATION AS TO THE
 FINISHED CEILING HEIGHTS, THE BATHROOM APPEARS TO HAVE
 A A/C AIR HANDLIER OR COIL UNIT, IS THIS UNIT ABOVE THE
 CEILING, OR LOCATED WITHIN A DRYWALLED AREA ABOVE THE
 RESTROOM CEILING. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 13) SHEET A3.1 ALSO INDICATES TO HAVE A AIR COMPRESSOR
 LOCATED WEST OF THE 2 STORY AREA, THIS COMPRESSOR WOULD
 BE LOCATED ON THE FIRST FLOOR ROOF REQUIRING A A/C
 STAND. PRE-MANUFACTURED A/C STANDS WILL REQUIRE PRODUCT
 APPROVALS, FL ADMINISTRATIVE RULE 9B-72 (31)(G).
  
 14) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4. FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4,
 1714.5.1 & EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A
 COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM BAR REINFORCING REQUIREMENTS, WALL PRESSURE
 ZONES, SLAT TYPES, ETC., SHALL BE SUBMITTED AT TIME OF
 PERMIT APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 A SAMPLE SCHEDULE IS ATTACHED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved