| 2009-11-30 15:49:12 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PROVIDE MANUFACTURER'S DATA SHOWING EXHAUST AND |
| | MAKEUP AIR FANS ARE DESIGNED FOR WIND RESISTANCE IN |
| | ACCORDANCE WITH FBC-M 301.12. IF MANUFACTURER'S WIND |
| | RESISTANCE DATA INCLUDES INSTALLATION INSTRUCTIONS, |
| | COORDINATE PLANS WITH THE MANUFACTURER'S INSTRUCTIONS |
| | PER FBC-M 304.1. |
| | |
| | 2. MUA DUCT SUPPORT DETAIL IS INSUFFICIENT. EXAMPLE: |
| | THERE IS NO INDICATION AS TO THE SIZE, THICKNESS OR |
| | MATERIAL FOR THE ANGLE SUPPORT LEGS. EXAMPLE: DETAIL |
| | CALLS FOR SCREWS AT 12 INCHES ON-CENTER TO ATTACH LEGS |
| | TO ROOF. PLEASE INDICATE THE NUMBER AND LOCATION OF |
| | FASTENERS IN THE DETAIL AT THIS POINT. ALSO, SHOW HOW |
| | THE ANGLES ARE TO BE ATTACHED TO EACH OTHER AT THE BASE |
| | OF THE LEGS AND AT THE CORNERS OF THE DUCTS. PROVIDE |
| | SUFFICIENT DETAIL FOR EACH TYPE OF MATERIAL AND EACH |
| | TYPE OF CONNECTION TO BE USED IN ACCORDANCE WITH FBC-M |
| | 301.12. |
| | |
| | 3. GREASE DUCT AND HOOD APPEAR TO BE IN CLOSE PROXIMITY |
| | TO WOOD CONSTRUCTION AT ROOF/CEILING ASSEMBLY. SHOW |
| | PROPER CLEARANCES ON PLAN OR PROVIDE DETAIL FOR ANY |
| | PROPOSE CLEARANCE REDUCTION METHODS TO BE USED IN |
| | ACCORDANCE WITH FBC-M 506.3.6. |
| | |
| | 4. GUARDS SHALL BE INSTALLED AT ROOF EDGE WHERE NEW |
| | EQUIPMENT IS INSTALLED WITHIN 10 FEET OF THE ROOF EDGE |
| | IN ACCORDANCE WITH FBC-M 304.10. |
| | |
| | 5. TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED |
| | TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER |
| | COOKING OPERATIONS OCCUR IN ACCORDANCE WITH FBC-M |
| | 507.2.1.1. THE ACTIVATION OF THE EXHAUST FAN SHALL |
| | OCCUR THROUGH AN INTERLOCK WITH THE COOKING APPLIANCES, |
| | BY MEANS OF HEAT SENSORS OR BY MEANS OF OTHER APPROVED |
| | METHODS. |
| | |
| | 6. PROVIDE ELEVATION DRAWINGS WITH PHOTOGRAPHIC |
| | DEPICTIONS OF EXISTING CONDITIONS TO FACILITATE A |
| | ZONING PLAN REVIEW FOR SCREENING AND OTHER MUNICIPAL |
| | REQUIREMENTS. A ZONING REVIEW IS NOT BEING PERFORMED AT |
| | THIS TIME DUE TO LACKING INFORMATION. |
| | |