| Plan Review Notes For Permit 09110336 |
| Permit Number |
09110336 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-13 17:22:31 | *****PARTIAL APPROVAL***** | | | | | | PLAN APPEARS TO BE CODE COMPLIANT; THE APPROPIATE | | | SHEETS TO BE FIRE-STAMPED WHEN THE FOLLOWING HAVE BEEN | | | SATISFIED: | | | | | | 1. A CONTRACTOR IS SIGNED ON AND LICENSURE IS VERIFIED. | | | | | | 2. ON SHEET T-1, AMEND TO REFLECT THE CURRENT CODES IN | | | USE AS SUCH: FLORIDA FIRE PREVENTION CODE 2007 AND NFPA | | | 101, LIFE SAFETY CODE, 2006 EDITIONS. | | | | | | 3. ON THE APPROPIATE PLAN SHEET, REFERENCE 7.1.3.2.1 | | | (6) OF NFPA 101 AS IT PERTAINS TO THE LIMITING OF | | | PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT | | | ENCLOSURE ASSEMBLY. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|