Plan Review Notes
Plan Review Notes For Permit 09110336
Permit Number 09110336
Review Stop E
Sequence Number 1
Notes
Date Text
2009-12-09 13:58:19 
 ** DENIED **
  
 ** REVIEW UNDER 2008 NEC.
  
 1) NOTE: PLEASE PROVIDE COPY OF CONTRACT FOR ALL NEW
 WORK AS SHOWN ON PLANS. THE VALUE FOR THE COMPLETE
 SCOPE OF WORK AS SHOWN IS LOW. FBC 108.3 REQUIRES THE
 VALUE TO INCLUDE ALL LABOR, EQUIPMENT, MATERIALS,
 DESIGN COST ETC EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
  
 2) NOTE: PLEASE KNOW THE FOLLOWING CODE WHICH IS
 RELEVANT TO THE DESIGN SHOULD BE ON PLANS.
 2008 NFPA-70 (PLANS DO NOT INDICATE ANY SPECIFIC
 EDITION ON COVER SHEET)
 2006 NFPA-101 (PLANS INDICATE THE 2003. FAC
 69A-60.003,.004 ADOPTED THE 2006 ON DECEMBER 31ST,
 2008.
 2007 FLORIDA FIRE PREVENTION CODE (PLANS INDICATE THE
 2004 EDITION.
  
 3) NOTE: NOT APPLIED FOR PERMIT BY A LICENSED
 CONTRACTOR FOR SCOPE OF WORK. LICENSURE INFORMATION
 WILL NEED TO BE VERIFIED WHEN CONTRACTOR HAS BEEN
 DETERMINED.
  
 4) NOTE: PLEASE INDICATE ANY ROUTING OF CONDUITS DOWN
 THROUGH THE BUILDING. PLEASE BE SURE TO SEE CHAPTER 10
 OF THE FBC AS CONDUITS ARE NOT PERMITTED IN EGRESS
 STAIRS.
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  