| Plan Review Notes For Permit 09110301 |
| Permit Number |
09110301 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-01-04 10:47:14 | ** TEMPORARY DENIED * | | | | | | ** THE NOTE #1 BELOW NEEDS TO BE ADDRESSED AT THIS | | | TIME. THE NOTE #2 WILL BE PART OF THE PROVISO AS | | | REFERENCED ON THE INITIAL REVIEW. | | | | | | | | | 1) NOTE: THE SECOND COPY OF THE SUBMITTED FLA COM | | | CALCULATIONS IS IN FACT A PHOTO-COPY OF SIGNED AND SEAL | | | DOCUMENTS. PLEASE SUBMIT SECOND SET OF ORIGINAL SIGNED, | | | DATED AND SEALED CALCULATIONS. | | | FAC 61G15-23.002, FS 471.025 | | | | | | 2) NOTE: ALL PANEL SCHEDULES WILL BE UPDATED TO BE | | | SPECIFIC TO ALL ROOMS AND AREAS IN WHICH THEY FEED. | | | 408.4. | | | PLACING * LIGHTING OR RECEPTACLES* IN GENERAL IN NOT | | | ACCEPTABLE FOR PANEL SCHEDULES ON RECORD PLANS. ALL | | | OTHER CHANGES ARE TO BE REVISED AND SUBMITTED BEFORE | | | ROUGH INSPECTIONS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | |
|