Plan Review Notes
Plan Review Notes For Permit 09110301
Permit Number 09110301
Review Stop E
Sequence Number 1
Notes
Date Text
2010-01-11 10:17:09 
 ** DENIED **
  
 ** SOME ITEMS BELOW COULD HAVE BEEN REDLINED HOWEVER
 NOT ALL. PLEASE ADDRESS COMMENTS AT THIS TIME.
  
 1) NOTE: *PLEASE ADJUST CODES AS FOLLOWS FOR THIS
 REVIEWER AS APPLICABLE. SOME OTHER CODES MAY BE NOTED
 BY OTHER TRADES.
 PLANS INDICATE 2004 FBC ON SOME OF THE ARCHITECTURAL
 SHEETS AS WELL AS OLDER NFPA-1 AND NFPA-101 EDITIONS.
 SEE A100, A130 ETC.
 ELECTRICAL SHEETS INDICATE THE 2005 NFPA-70.
 PLEASE BE SURE THE FOLLOWING RELEVANT CODES ARE
 ADJUSTED ON SHEETS
  
 THE 2008 NFPA-70: ADOPTED ON OCTOBER 1ST, 2009. PLEASE
 ADJUST DESIGNS FOR NEW REVISED CODES.
 2006 NFPA-101: ADOPTED 12/31/08 BY FAC 69A-60.004
 2002 NFPA-72: ADOPTED 12/31/08 FAC 69A-3.012
 2006 NFPA-1: ADOPTED 12/31/08 FAC 69A-60.003( TO BE
 NOTED BY FIRE REVIEW
 2007 FLORIDA FIRE PREVENTION CODE. ( TO BE NOTED BY
 FIRE REVIEW) PLANS STATE 2006 FFPC.
  
  
 2) NOTE: PLEASE CLARIFY THE OCCUPANCY OF THIS BUILDING
 OUT PER FBC CHAPTER 3. THE PLANS APPEAR TO INDICATE
 BUSINESS HOWEVER THE COVER SHEET ALSO INDICATES A
 MEDICAL STORE. IS THIS MERCANTILE OR BUSINESS OFFICES?
 THIS WILL AFFECT THE LIGHTING ALLOWANCES.
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR REVIEW. NONE SUBMITTED FOR MINIMUM
 CODE COMPLIANCE.
 13-415.AB.5, 13-400.0.B.4, 13-400.2
  
 4) NOTE: PLEASE SEE 408.4 IN THE NEC. THE PANEL
 SCHEDULE WILL BE REQUIRED TO BE UPDATED WITH ALL
 CIRCUITS. PLANS WILL ALSO BE REQUIRED TO HAVE ALL
 CIRCUITS LABELED AND COORDINATED WITH PANEL SCHEDULES.
 THE USE OR WORDING OF *LIGHTING* OR *RECEPTACLES* IS
 NOT ACCEPTABLE. THE FOLLOWING IS EXTRACTED DIRECTLY
 FROM THE NEC HANDBOOK.
 **
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.**
  
 ** AS THIS IS AN EXISTING SITUATION A PROVISO CAN BE
 SET UP TO SUBMIT COMPLETE REVISED PANEL SCHEDULES AND
 CIRCUITING ON PLANS FOR ALL EXISTING AND NEW BEFORE
 FINAL.
 ALL NEW IS REQUIRED TO BE COORDINATED AT THIS TIME FOR
 ALL NEW RECEPTACLES, LIGHTING AND EQUIPMENT.
 ALL REVIEW OF LOADING ON CIRCUITS WILL BE DONE ONCE
 PLANS HAVE BEEN REVISED AND COORDINATED WITH PANEL
 SCHEDULES.
  
 5) NOTE: ALL LOW VOLTAGE IS UNDER SEPARATE PERMITS. ANY
 ACCESS CONTROL SYSTEM WILL ALSO BE UNDER SEPARATE
 PERMIT WITH SUBMISSION OF SEPARATE PLANS FOR DETAILS OF
 ACCESS CONTROLS MEETING NFPA-101 CHAPTER 7.
  
 6) NOTE: NEW OR EXISTING SIGN CIRCUIT REQUIRED PER
 600.5.
  
 7) NOTE: RISER INDICATES FEEDERS TO TRANSFORMER FROM
 PANEL H1A, HOWEVER THE PANEL IS NOTED AS H1SA.
 (MISPRINT)
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2009-12-13 17:47:22*****FIRE REVIEW, DENIED*****
  
 1. THE SUITE NUMBER SHALL BE INCLUDED IN THE PROJECT
 ADDRESS LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 2. AS OF DECEMBER 31, 2008, THE 2007 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE BASED ON NFPA 1, UNIFORM
 FIRE CODE, 2006 EDITION AND NFPA 101, LIFE SAFETY CODE,
 2006 EDITION SHALL BE REFERENCED. AMEND THE CODE
 SECTIONS LISTED ON THE AFFECTED SHEETS TO REFLECT THE
 EDITIONS CURRENTLY ADOPTED.
  
 3. ON SHEET FS2.1, PROVIDE A LAYOUT OF THE FIRE
 SPRINKLER HEADS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW