| 2010-03-17 09:14:12 | MARRIOTT HOME CARE |
| | 2700 BROADWAY AVENUE |
| | PERMIT # 09110297 |
| | |
| | 1. "OUTSIDE STAIRS AND LANDINGS, OTHER THAN EXISTING |
| | OUTSIDE STAIRS AND LANDINGS, SHALL BE DESIGNED TO |
| | MINIMIZE WATER ACCUMULATIONS ON THEIR SURFACES" RE: |
| | FFPC SECTION 7.2..2.6.5 |
| | |
| | 2. "WHERE APPROVED BY THE AHJ, EXITS SHALL BE PERMITTED |
| | TO DISCHARGE TO ROOFS OR OTHER SECTIONS OF THE BUILDING |
| | OR AN ADJOINING BUILDING WHERE THE FOLLOWING CRITERIA |
| | ARE MET |
| | |
| | (A) THE ROOF / CEILING ASSEMBLY CONSTRUCTION HAS A FIRE |
| | RESISTANCE RATING NOT LESS THAN THAT REQUIRED FOR THE |
| | EXIT ENCLOSURE" RE: FFPC SECTION 7.7.6 |
| | |
| | 3. EMERGENCY LIGHTING IS REQUIRED PER FFPC SECTION |
| | 7.9.1.2. |
| | |
| | 4. "STAIR TREADS AND LANDINGS SHALL BE FREE OF |
| | PROJECTIONS OR LIPS THAT COULD TRIP STAIR USERS" RE: |
| | FFPC SECTION 7.2.2.3.3.2 |
| | |
| | 5. " GUARDS IN ACCORDANCE WITH 7.2.2.4 SHALL BE |
| | PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS THAT |
| | EXCEED 30 INCHES ABOVE THE FLOOR OR GRADE BELOW" RE: |
| | FFPC SECTION 7.2.2.4 |
| | |
| | 6. "OPEN GUARDS SHALL HAVE INTERMEDIATE RAILS OR AN |
| | ORNAMENTAL PATTERN SUCH THAT A SPHERE 4 IN. IN DIAMETER |
| | IS NOT ABLE TO PASS THROUGH ANY OPENING UP TO A HEIGHT |
| | OF 34 IN. AND THE FOLLOWING SHALL ALSO APPLY |
| | |
| | (A) THE TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD, |
| | AND BOTTOM ELEMENT OF A GUARDRAIL AT THE OPEN SIDE OF A |
| | STAIR SHALL BE SUCH SIZE THAT A SPHERE 6 IN. IN |
| | DIAMETER IS NOT ABLE TO PASS THROUGH THE TRIANGULAR |
| | OPENING". RE: FFPC SECTION 7.2.2.4.5.3 |
| | |
| | 7. NEW EXIT DOOR HARDWARE SHALL BE EQUIPPED WITH |
| | HARDWARE THAT DOES NOT REQUIRE THE USE OF A KEY, TOOL, |
| | SPECIAL KNOWLDEGE OR EFFORT FROM INSIDE THE BUILDING. |
| | |
| | 8. EXIT SIGN AND EMERGENCY LIGHT REQUIRED OVER NEW EXIT |
| | DOOR. |
| | |
| | 9. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR HANDRAILS AND GUARDRAILS. |
| | |
| | 10. NEW STAIRS SHALL HAVE NO MORE THAN 12 FEET BETWEEN |
| | LANDINGS. RE: FFPC SECTION 7.2.2.2.1.1.A |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |