| Plan Review Notes For Permit 09110285 |
| Permit Number |
09110285 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-01-06 16:51:28 | | | | | | | PASSED/PROVISO: | | | | | | SHT P1.01 SANITARY RISER DIAGRAM DOES NOT REFLECT THE | | | FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS. THE | | | FLOOR PLAN SHOWS ONE BLDG DRAIN WITH A DOUBLE WYE | | | PICKING UP BOTH TOILET ROOMS. BUT THE RISER SHOWS BOTH | | | TOILET ROOMS EXITING THE BUILDING SEPARATELY. -- THE | | | TRAPS FOR THE W/C'S ARE NOT APPROVED AS THE W/C'S HAVE | | | INTEGRAL TRAPS AND DOUBLE TRAPING IS NOT APPROVED PER | | | SECTION 1002.1. -- THE TRAPS FOR THE LAVS ARE INDICATED | | | AS UNDER THE SLAB ON THE RISER DIAGRAM. | | | | | | SHT P1.01 THE WATER RISER DIAGRAM DOES NOT SHOW THE | | | WATER SUPPLY TO EITHER W/C. | | | | | | A REVISION IS REQUIRED TO CORRECT THESE DIFICENCIES AND | | | REFLECT THE INSTALLATION. | | | | | | | | | | | | 1-14-10 | | | CHANGED TO FAILED STATUS BECAUSE 2ND SET OF PLANS IS | | | MISSING SHEETS S1.01, THE ORIGINAL P1.01 PLUMBING PLAN, | | | E1.01 & D1.01. WHEN TWO FULL SETS OF PLANS ARE | | | SUBMITTED THEN THE STATUS WILL CHANGE. | | | | | | | | | | | | | | | | | | . |
|