| Plan Review Notes For Permit 09110285 |
| Permit Number |
09110285 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-01-14 13:19:06 | *****DENIED***** | | | | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS PLAN | | | REVIEW HAVE NOT BEEN ADDRESSED: | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | SHALL COMPLY WITH NFPA 241 - 2004 EDITION. | | | | | | 2. DEBRIS FROM DEMOLITION SHALL BE REMOVED FROM THE | | | SITE DAILY. | | | | | | 3. THE ELEVATION DRAWINGS DO NOT REVEAL THE BUILDING | | | ADDRESS. THE ADDRESS NUMBERS SHALL BE A MINIMUM OF AT | | | LEAST 6" IN HEIGHT AND AT LEAST 1" IN WIDTH. THESE | | | NUMBERS SHOULD CONTRAST TO THE BACKGROUND THAT THEY ARE | | | AFFIXED. | | | | | | 4. PLEASE ENSURE THAT ALL EXISTING EMERGENCY LIGHTS AND | | | EXITS SIGNS ARE IN WORKING CONDITION. | | | | | | 5. SPECIFY THE INTERIOR FINISH CLASSIFICATIONS FOR | | | WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR | | | CLASS C. | | | | | | 6. PLEASE INDICATE PORTABLE FIRE EXTINGUISHER | | | LOCATIONS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED ON THE | | | PLANS | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|