Plan Review Notes
Plan Review Notes For Permit 09110277
Permit Number 09110277
Review Stop E
Sequence Number 2
Notes
Date Text
2010-01-28 14:06:57 
 ** DENIED SECOND REVIEW *
  
 ** THIS REVIEWER ATTEMPTED TO CONTACT ARCHITECT OF
 RECORD HOWEVER PHONE NUMBERS LISTED ON RESPONSE LETTER
 AND PLANS IS DISCONNECTED.
  
 1) NOTE: THE RESPONSE LETTER FOR SOME ITEMS DID NOT
 SEEM TO RESPOND TO THE ACTUAL COMMENT. THE SCOPE ON
 PREVIOUS PLANS WAS UNCLEAR AND WE NEEDED MORE
 INFORMATION FOR REVIEW. A PREVIOUS COMMENT WAS MADE
 ABOUT COMPLIANCE FOR CHAPTER 13. HOWEVER THE RESPONSE
 WAS THAT THE MECHANICAL SYSTEMS WERE NOT BEING ALTERED.
 PLEASE SEE CHAPTER 13 OF THE FLORIDA BUILDING CODE.
 CHAPTER 13 COVERS MANY ITEMS WHICH ARE NOT MECHANICAL
 SYSTEMS. RESPONSE MENTIONS MECHANICAL SYSTEMS HOWEVER
 SPECIFIC CODE SECTIONS FOR OTHER ITEMS LISTED BELOW
 WERE GIVEN ON PREVIOUS NOTES WHICH WERE NOT ABOUT
 MECHANICAL SYSTEMS.
 FOR EXAMPLE:
 PLEASE SEE 13-413 FOR REQUIREMENTS FOR ELECTRICAL
 POWER.
 PLEASE SEE 13-415.AB.5 FOR THE REQUIREMENTS FOR
 LIGHTING PERFORMANCE CALCULATIONS FOR NEW LIGHTING
 MEETING PRESCRIPTIVE REQUIREMENTS. IN BRIEF EVEN WHEN
 NOT MEETING THE DEFINITION OF A RENOVATION AS DEFINED
 IN SECTION 202, THE NEW BEING INSTALLED IS STILL
 REQUIRED TO MEET MINIMUM PRESCRIPTIVE REQUIREMENTS.
 13-400.0.B.4
 PLEASE SEE 13-415.AB.1.1,.1.2 AND .1.3 FOR INTERIOR
 LIGHTING CONTROLS WHERE REQUIRED. ANY SEPARATE SPACES,
 NEW CONTROLS INSTALLED OR SEPARATE SPACE CONTROLS ARE
 REQUIRED TO MEET MINIMUMS.
  
 FOR EXAMPLE: ANOTHER NOTE FROM PREVIOUS REVIEW WAS WITH
 RESPECT TO CHAPTER 11 REQUIREMENTS. THE RESPONSE NOTED
 REQUIREMENTS FOR ADA OF BATHROOMS, LAVATORIES ETC
 HOWEVER THERE ARE OTHER ITEMS IN CHAPTER 11 WHICH ARE
 REQUIRED FOR MINIMUM ADA COMPLIANCE WHICH ARE NOT ONLY
 BATHROOMS, DOORS ETC. THIS WAS GIVEN IN PREVIOUS REVIEW
 HOWEVER RESPONSE DID NOT RESPOND TO FA DEVICES FOR ADA.
 PLEASE PROVIDE INFORMATION ON ANY HORN, STROBE DEVICES,
 LOCATIONS AND HEIGHTS IN COMPLIANCE WITH 11-4.28,.1, .2
 AND .3.
 THIS FACILITY DOES HAVE A FIRE ALARM SYSTEM AND BASE
 DESIGN INTENT FOR MINIMUMS NEED TO BE SHOWN.
 WHERE ARE THE DEVICES, WILL NEW WORK AFFECTING THE
 DEVICES?
 BASED ON THE PLANS NEW WORK WILL AFFECT THE DEVICES.
  
  
 2) NOTE: SHOW LOCATIONS OF EXISTING OR NEW EMERGENCY
 LIGHTING MEETING NFPA-101 7.8, 7.9. FBC 1006.1, 1006.2
 AND 1006.3.
 PLACING A NOTE ON PLANS FOR THIS TO BE VERIFIED DOES
 NOT PROVIDE MINIMUM INFORMATION.
 EXIT LIGHTING PLACEMENT WILL BE UNDER FIRE MARSHAL
 REVIEW.
 NOTES ON PLANS MENTIONS EXIT LIGHTS TO BE CIRCUITED TO
 EXISTING EMERGENCY LIGHT CIRCUIT. PLEASE SEE NEC
 700.12F FOR ANY NEW OR EXISTING EMERGENCY LIGHTS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  