| 2010-01-28 14:06:57 | |
| | ** DENIED SECOND REVIEW * |
| | |
| | ** THIS REVIEWER ATTEMPTED TO CONTACT ARCHITECT OF |
| | RECORD HOWEVER PHONE NUMBERS LISTED ON RESPONSE LETTER |
| | AND PLANS IS DISCONNECTED. |
| | |
| | 1) NOTE: THE RESPONSE LETTER FOR SOME ITEMS DID NOT |
| | SEEM TO RESPOND TO THE ACTUAL COMMENT. THE SCOPE ON |
| | PREVIOUS PLANS WAS UNCLEAR AND WE NEEDED MORE |
| | INFORMATION FOR REVIEW. A PREVIOUS COMMENT WAS MADE |
| | ABOUT COMPLIANCE FOR CHAPTER 13. HOWEVER THE RESPONSE |
| | WAS THAT THE MECHANICAL SYSTEMS WERE NOT BEING ALTERED. |
| | PLEASE SEE CHAPTER 13 OF THE FLORIDA BUILDING CODE. |
| | CHAPTER 13 COVERS MANY ITEMS WHICH ARE NOT MECHANICAL |
| | SYSTEMS. RESPONSE MENTIONS MECHANICAL SYSTEMS HOWEVER |
| | SPECIFIC CODE SECTIONS FOR OTHER ITEMS LISTED BELOW |
| | WERE GIVEN ON PREVIOUS NOTES WHICH WERE NOT ABOUT |
| | MECHANICAL SYSTEMS. |
| | FOR EXAMPLE: |
| | PLEASE SEE 13-413 FOR REQUIREMENTS FOR ELECTRICAL |
| | POWER. |
| | PLEASE SEE 13-415.AB.5 FOR THE REQUIREMENTS FOR |
| | LIGHTING PERFORMANCE CALCULATIONS FOR NEW LIGHTING |
| | MEETING PRESCRIPTIVE REQUIREMENTS. IN BRIEF EVEN WHEN |
| | NOT MEETING THE DEFINITION OF A RENOVATION AS DEFINED |
| | IN SECTION 202, THE NEW BEING INSTALLED IS STILL |
| | REQUIRED TO MEET MINIMUM PRESCRIPTIVE REQUIREMENTS. |
| | 13-400.0.B.4 |
| | PLEASE SEE 13-415.AB.1.1,.1.2 AND .1.3 FOR INTERIOR |
| | LIGHTING CONTROLS WHERE REQUIRED. ANY SEPARATE SPACES, |
| | NEW CONTROLS INSTALLED OR SEPARATE SPACE CONTROLS ARE |
| | REQUIRED TO MEET MINIMUMS. |
| | |
| | FOR EXAMPLE: ANOTHER NOTE FROM PREVIOUS REVIEW WAS WITH |
| | RESPECT TO CHAPTER 11 REQUIREMENTS. THE RESPONSE NOTED |
| | REQUIREMENTS FOR ADA OF BATHROOMS, LAVATORIES ETC |
| | HOWEVER THERE ARE OTHER ITEMS IN CHAPTER 11 WHICH ARE |
| | REQUIRED FOR MINIMUM ADA COMPLIANCE WHICH ARE NOT ONLY |
| | BATHROOMS, DOORS ETC. THIS WAS GIVEN IN PREVIOUS REVIEW |
| | HOWEVER RESPONSE DID NOT RESPOND TO FA DEVICES FOR ADA. |
| | PLEASE PROVIDE INFORMATION ON ANY HORN, STROBE DEVICES, |
| | LOCATIONS AND HEIGHTS IN COMPLIANCE WITH 11-4.28,.1, .2 |
| | AND .3. |
| | THIS FACILITY DOES HAVE A FIRE ALARM SYSTEM AND BASE |
| | DESIGN INTENT FOR MINIMUMS NEED TO BE SHOWN. |
| | WHERE ARE THE DEVICES, WILL NEW WORK AFFECTING THE |
| | DEVICES? |
| | BASED ON THE PLANS NEW WORK WILL AFFECT THE DEVICES. |
| | |
| | |
| | 2) NOTE: SHOW LOCATIONS OF EXISTING OR NEW EMERGENCY |
| | LIGHTING MEETING NFPA-101 7.8, 7.9. FBC 1006.1, 1006.2 |
| | AND 1006.3. |
| | PLACING A NOTE ON PLANS FOR THIS TO BE VERIFIED DOES |
| | NOT PROVIDE MINIMUM INFORMATION. |
| | EXIT LIGHTING PLACEMENT WILL BE UNDER FIRE MARSHAL |
| | REVIEW. |
| | NOTES ON PLANS MENTIONS EXIT LIGHTS TO BE CIRCUITED TO |
| | EXISTING EMERGENCY LIGHT CIRCUIT. PLEASE SEE NEC |
| | 700.12F FOR ANY NEW OR EXISTING EMERGENCY LIGHTS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |