Plan Review Notes
Plan Review Notes For Permit 09110277
Permit Number 09110277
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-12-27 21:18:55*****DENIED****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. AS OF 12/31/2008, THE 2007 FLORIDA FIRE PREVENTION
 CODE BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION
 AND NFPA 1, UNIFORM FIRE CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. THE SCOPE OF WORK FOR THIS PROJECT IS DESCRIBED (ON
 SHEET A00) AS TO THE COMMON AREAS ON THE BOTH THE FIRST
 AND SECOND FLOOR. NO PLANS INDICATED FOR THE SECOND
 FLOOR.
  
 4. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
 5. PROVIDE A LIFE SAFETY PLAN DEPICTING THE LOCATION OF
 EXIT LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHERS, AND
 TRAVEL DISTANCES TO THE EXITS.
  
 6. HOW WILL THE PROJECTED SCOPE OF WORK HAVE AFFECT ON
 THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEMS? SEPARATE
 PLANS AND PERMITS WILL BE REQUIRED FOR ANY REMODEL TO
 THESE LIFE SAFETY SYSTEMS.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722