Plan Review Notes
Plan Review Notes For Permit 09110277
Permit Number 09110277
Review Stop E
Sequence Number 1
Notes
Date Text
2009-12-03 14:39:59** DENIED**
  
 1) NOTE: THERE IS MINOR WORK WHICH WILL INVOLVE
 ELECTRICAL WORK HOWEVER NO ELECTRICAL DETAILS OR SCOPE
 SUBMITTED.
 PLANS INDICATE NEW CEILING IN SOME AREAS HOWEVER
 LIGHTING FIXTURE LAYOUT AND MINIMUM FOR COMPLIANCE NOT
 SHOWN OR SUBMITTED. PLEASE VERIFY SCOPE FOR THE
 FOLLOWING CURRENT CODES:
 2007 FBC W/2009 REVISIONS, SEE CHAPTER 13,
 13-415.AB.1.1,.1.2, 13-415.AB.5 FOR ENERGY COMPLIANCE
 AND CHAPTER 11, 11-4.28.1,.2 AND.3 FOR ADA.
 PLEASE SEE NFPA-101 2006 7.8.1.3, 7.9.1.2,.2.2 FOR
 MINIMUM REQUIRED FOR LIFE SAFETY FOR EGRESS.
 PLEASE SEE NFPA-70 700.12F FOR CIRCUITING OF EMERGENCY
 AND EXIT LIGHTS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  