| Plan Review Notes For Permit 09110267 |
| Permit Number |
09110267 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-03 15:25:42 | | | | ** DENIED** | | | | | | 1) NOTE: THE FOLLOWING CODES INDICATED ON THE SHEET ARE | | | NOT ADOPTED BY THE STATE OF FLORIDA. | | | PLANS LIST THE 2009 NFPA-101, HOWEVER THIS SHOULD BE | | | 2006. THIS COULD BE RED-LINED HOWEVER COMING BACK FOR | | | OTHER COMMENTS. | | | PLANS LIST A 2006 EDITION OF NFPA-70 ( NEC) HOWEVER | | | THIS SHOULD BE 2008. FOR INFORMATION THERE WAS NOT A | | | 2006 NEC. | | | | | | 2) NOTE: PLANS INDICATE NEW LIGHTING HOWEVER NO | | | INFORMATION ON TYPE OF LIGHTS, HOW MANY LIGHTS, AND | | | CONTROL OF LIGHTS ETC. | | | 13-415.AB.2 FOR EXTERIOR LIGHTING ALLOWANCES. | | | 13-415.AB.1.4 FOR TYPE OF CONTROL REQUIRED. | | | NEC 310.16,240.4, 220.12, 220.42 FOR LOADS, CIRCUITING | | | AND OVER CURRENT PROTECTION. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|