| Plan Review Notes For Permit 09110263 |
| Permit Number |
09110263 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-11-18 11:00:50 | BUILDING PROVISO:1207.3 STRUCTURE-BORNE SOUND. PROVIDE | | | DOCUMENTATION BEFORE INSPECTION. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | |
|