| 2009-12-09 08:47:16 | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| | |
| | 3. EXITS ARE TO REMAIN CLEAR AND ACCESSIBLE. |
| | |
| | 4. OCCUPANT LOAD WILL BE DETERMINED BY THIS OFFICE. |
| | |
| | 5. TACTILE SIGNAGE REQUIRED AT EXIT DOORS. |
| | |
| | 6. EMPLOYEES SHALL BE TRAINED IN CROWD MANAGEMENT |
| | PROCEDURES. PLEASE GO TO MARYLAND STATE FIRE MARSHAL'S |
| | WEB SITE AND CLICK ON THE CROWD MANAGEMENT TRAINING |
| | ICON. EMPLOYEES ARE TO WATCH THE TRAINING VIDEO AND |
| | COMPLETE THE TEST. CERTIFICATES ARE TO BE PROVIDED TO |
| | THIS OFFICE. |
| | |
| | 7. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR ALL HANDRAILS AND GUARDRAILS. |
| | |
| | 8. EXIT DOORS ON SOME SHEETS ARE SWINGING IN THE WRONG |
| | DIRECTION. |
| | |
| | 9. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD, |
| | DUCT, AND FIRE SUPPRESSION SYSTEMS. |
| | |
| | 10. INTERIOR FINISH MATERIALS SUCH AS THE THATCH ROOF |
| | MATERIALS SHALL BE FIRE RETARDANT. |
| | |
| | 11. PLANS INDICATE INTERIOR FINISH FOR A MERCANTILE |
| | OCCUPANCY. THE OCCUPANCY WILL BE AN ASSEBLY OCCUPANCY. |
| | |
| | 12. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A |
| | MINIMUM OF AT LEAST 6" HIGH AND AT LEAST 1" WIDE |
| | NUMBERS ARE REQUIRED. |
| | |
| | 13. PLEASE INDICATE SLIP RESISTANT METHODS PLANNED FOR |
| | THE EXTERIOR STAIRS. |
| | |
| | 14. NO FIRE SPRINKLER SYSTEM DRAWINGS PROVIDED. PLEASE |
| | PROVIDE FIRE SPRINKLER DRAWINGS AND HYDRAULIC |
| | CALCULATIONS. SEPARATE PLANS AND PERMITS REQUIRED. |
| | |
| | 15. NO FIRE ALARM SYSTEM INFORMATION PROVIDED. THE FIRE |
| | ALARM SYSTEM SHALL BE A VOICE EVACUATION TYPE. SEPARATE |
| | PLANS AND PERMITS REQUIRED. |
| | |
| | 16. NO DOOR SCHEDULE PROVIDED. PLEASE PROVIDE A DOOR |
| | SCHEDULE INDICATING THE TYPE OF HARDWARE PLANNED. EXIT |
| | DOORS SUBJECT TO AN OCCUPANT LOAD OF 100 OR MORE |
| | PERSONS SHALL BE EQUIPPED WITH PANIC HARDWARE. FIRE |
| | RATED DOORS SHALL BE EQUIPPED WITH LISTED FIRE RATED |
| | EXIT HARDWARE. ALL RATED DOORS SHALL BE EQUIPPED WITH |
| | SELF-CLOSING DEVICES. |
| | |
| | 17. PLEASE INDICATE RISE, RUN, AND TREAD DEPTH FOR ALL |
| | STAIRS. |
| | |
| | 18. DOOR OPENINGS OBSERVED ON WEST ELEVATION NEAR EXIT |
| | DOORS. |
| | |
| | 19. NO LIGHT FIXTURES OBSERVED FOR WEST EXIT STAIRS. |
| | |
| | 20. ALL COOLERS AND FREEZERS SHALL BE PROVIDED WITH |
| | FIRE SPRINKLER PROTECTION. |
| | |
| | 21. PLEASE INDICATE SEATING LOCATIONS FOR PHYSICALLY |
| | CHALLENGED PERSONS. |
| | |
| | 22. PLEASE PROVIDE FIRESTOPPING DETAILS. |
| | |
| | 23. PLEASE INDICATE HOURLY FIRE RATINGS OF EXISTING |
| | STAIRS AND ALL VERTICAL SHAFTS WHETHER NEW OR EXISTING. |
| | |
| | 24. ONE OF THE EXIT STAIRS TERMINATES INTO KITCHEN 109. |
| | PLEASE REVIEW EXITING THROUGH KITCHEN REQUIREMENTS. |
| | |
| | 25. ELEVATOR WARNING SIGNS ARE REQUIRED AT ELEVATOR |
| | LOCATIONS. |
| | |
| | 26. WHO'S PROPERTY DOES THE REAR EXIT STAIR TERMINATES |
| | ONTO. |
| | |
| | 27. EXISTING DOOR IS LOCATED WITHIN AN EXISTING STAIR. |
| | WHAT IS THE PURPOSE OF THIS DOOR. SINCE NO EXITING |
| | OCCURS THIS AREA NEEDS TO BE SEALED. |
| | |
| | 28. SOME BUILDING ELEMENTS AND FURNITURE APPEAR TO BE |
| | LOCATED OVER THE PROPERTY LINE. AIR RIGHTS APPEAR TO BE |
| | REQUIRED. |
| | |
| | 29. PLEASE ILLUSTRATE ANY NATURAL GAS SUPPLY LINES AND |
| | APPURTENANT EQUIPMENT. |
| | |
| | DENIED. |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |