| 2009-11-24 15:05:05 | SIGN, BUILDING REVIEW CHECKLIST. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- ENGINEERED DRAWINGS ARE INCOMPLETE: |
| | |
| | A) ENGINEER TO PROVIDE THE DESIGN CALCULATIONS FOR THE |
| | MONUMENTAL SIGN SHOWING COMPLIANCE WITH ASCE 7-05. SEC. |
| | 106.1.2 OF CITY AMENDMENTS TO FBC. |
| | |
| | B) SPECIFY ATTACHMENT OF 6" STEEL PIPE TO THE SIGN |
| | FRAME TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF |
| | ASCE 7-05. |
| | ALSO, SPECIFY HOW MUCH EMBEDMENT OF STEEL PIPE INTO |
| | CONCRETE. PROVIDE SPECIFICATIONS FOR TYPE OF CONCRETE. |
| | AND REINFORCEMENT. SPECIFY SIZE OF FOOTING (SPECIFY ALL |
| | SIDES). |
| | |
| | C) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS FOR |
| | CONSTRUCTION OF MONUMENTAL SIGN TO VERIFY COMPLIANCE |
| | WITH THE DESIGN PRESSURES OF ASCE 7-05. SPECIFY ALL |
| | MATERIALS AND ATTACHMENT. SPECIFY ALL SIGN MATERIALS |
| | AND ATTACHMENTS. . SPECIFY ALL FRAMING MEMBERS AND |
| | DIMENSIONS. PROVIDE COMPLETE ELEVATIONS/SECTIONS |
| | SHOWING ALL THE SIDES OF THE MONUMENTAL SIGN AND |
| | DIMENSIONS. SEC. 106.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. UPDATE VALUE TO |
| | INCLUDE ALL LABOR, MATERIALS AND ENGINEERING. PROVIDE |
| | COPY OF SIGNED CONTRACTS. |
| | |
| | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |
| | |
| | |