| Plan Review Notes For Permit 09110205 |
| Permit Number |
09110205 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-12-22 13:27:22 | 2007 FBC W/2009 REVISIONS | | | NEW RESIDENTIAL POOL | | | | | | DENIED BY BUILDING | | | | | | 1) ITEMS 2,3 FROM THE FIRST REVIEW WERE NOT ADDRESSED. | | | | | | 2) THE TURNOVER RATE SPECIFIED ON THE PLANS IS 2.2 HRS. | | | FOR A 14,178 GALLON POOL. THIS WILL REQUIRE A FLOW RATE | | | OF 107.4 GPM. THE PUMP SPECIFIED HAS A MAXIMUM FLOW | | | RATE OF 102 GPM. PLEASE REVISE. FBC R 4101.20 ALLOWS UP | | | TO 12 HOURS FOR TURNOVER. IN ORDER TO DETERMINE THE | | | TURNOVER RATE YOU WILL NEED TO KNOW THE TDH. | | | | | | 3) AT A FLOW RATE OF 102 GALLONS PER MINUTE THAT IS | | | SPECIFIED ON THE PLANS, THE 2.5" BRANCH PIPING BETWEEN | | | THE TWO MAIN DRAINS EXCEEDS THE 6 FT/SEC ALLOWED BY | | | ANSI/APSP-7. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|