| 2009-12-03 09:33:54 | 2007 FBC W/2009 REVISIONS | | | NEW RESIDENTIAL POOL | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS WITH A PUMP CURVE CHART FOR THE PUMP | | | THAT WILL BE INSTALLED. | | | | | | 2) SPECIFY THE THE TOTAL DYNAMIC HEAD FOR THE POOL | | | CIRCULATION SYSTEM. PROVIDE TWO COPIES OF THE | | | CALCULATIONS SHOWING HOW TDH WAS DETERMINED. | | | | | | 3) SPECIFY THE FLOW RATE FOR THE PUMP IN GPM AT THE TDH | | | DETERMINED FOR THE SYSTEM ON THE PLANS. | | | | | | 4) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS, | | | FLOW RATING AND LISTING FOR THE MAIN DRAIN SUCTION | | | OUTLETS THAT WILL BE INSTALLED. | | | | | | 5) NOTE: THE EXISTING FENCE AND THE BARRIER BETWEEN THE | | | DWELLING AND THE POOL ARE REQUIRED TO COMPLY WITH THE | | | BARRIER OF FBC R4101.17. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|