| 2010-01-06 16:57:43 | ** CALCULATIONS MAILED STANDARD MAIL 12/22. THESE WERE |
| | LOCATED IN OFFICE WITH NO DATE STAMP WHEN RECEIVED. |
| | LOCATED ON 1/4/10 |
| | |
| | ** DENIED ** |
| | |
| | |
| | 1) NOTE: THE NEW SUBMITTED ENERGY PERFORMANCE |
| | CALCULATIONS ARE NOT COORDINATING WITH PLANS. A CALL |
| | WAS PLACED TO ENGINEERING FIRM TO GO OVER COMMENTS, |
| | FIXTURES ETC. |
| | THERE ARE FIXTURES WHICH ARE NOT ON THE INPUT DATA |
| | REPORT. |
| | TRACK LIGHTING IS REQUIRED TO BE FIGURED AT THE WATTAGE |
| | PER EACH FIXTURE TIMES THE NUMBER OF FIXTURES OR 30VA |
| | PER FT (WHICHEVER IS GREATER). PLEASE SEE 13-415.AB.5, |
| | AND APPENDIX B4.1.1 |
| | ** SOME FIXTURES SUCH AS S TYPE NEED TO BE INCLUDED. |
| | ** THE W FIXTURES ARE NOT LISTED ON THE FIXTURE LEGEND |
| | AS ANY SPECIFIC WATTAGE OR FIXTURE. BASED ON |
| | CONVERSATION WITH ENGINEER PLANS CAN BE REDLINED BY |
| | THIS OFFICE FOR A MAXIMUM WATTAGE FIXTURE HOWEVER THAT |
| | WATTAGE NEEDS TO BE INCLUDED ON THE IDR. |
| | ** THE T FIXTURES WHICH DO NOT FALL UNDER EXEMPTIONS IN |
| | 13-415.AB.5 NEED TO BE INCLUDED. ( T3). |
| | ** THERE ARE NO P1 FIXTURES LISTED. |
| | ** THERE ARE NO P2 FIXTURES LISTED. |
| | ** ANY S OR S2 FIXTURES WHICH ARE ON FOR GENERAL |
| | LIGHTING AND ALSO COME ON FOR BATTERY BACK ARE REQUIRED |
| | TO BE INCLUDED. ONLY FIXTURES WHICH DO COME ON FOR ANY |
| | GENERAL LIGHTING PURPOSE AND ONLY COME ON DURING POWER |
| | FAILURE ARE NOT INCLUDED. |
| | ** D FIXTURES? |
| | ** PLEASE REVISE METHOD OF CONTROLS. THE IDR SHOWS |
| | MANUAL ON/OFF WHEN PLANS INDICATE AUTOMATED LIGHTING |
| | CONTROLS. ( THIS WOULD BE REDLINED IF ONLY ITEM. |
| | ** PLEASE EXPLAIN THE 32-200W METAL HALIDES SHOWN ON |
| | THE IDR AND THE 4-250 METAL HALIDES SHOWN ON THE IDR. |
| | WHERE ARE THESE FIXTURES ON THE PLANS? |
| | |
| | |
| | PLEASE CALL TO GO OVER FOR ANY QUESTIONS. THE |
| | ALLOWANCES UNDER THE 2007 FBC W/ 2009 SUPPLEMENTS HAVE |
| | COMPLETELY CHANGED FROM PREVIOUS CODES. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |