| Plan Review Notes For Permit 09110183 |
| Permit Number |
09110183 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-04 12:37:48 | *****PARTIAL APPROVAL***** | | | | | | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE | | | OTHER TRADE REVIEWER'S COMMENTS AS WELL AS THE | | | FOLLOWING FIRE COMMENTS HAVE BEEN ADDRESSED: | | | | | | 1. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE | | | BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND | | | NFPA 1, UNIFORM FIRE CODE, 2006 EDITION SHALL BE | | | REFERENCED. ADD TO CODE SECTION | | | | | | 2. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW | | | ACOUSTICAL CEILING IN TERMS OF CLASS A, CLASS B, OR | | | CLASS C. ADD TO THE APPROPIATE PLAN SHEET | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | L;ETTER INDICATING WHERE THE ABOVE FIRE COMMENTS WERE | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | |
|