| Date |
Text |
| 2009-12-07 11:05:30 | BUILDING PLAN REVIEW |
| | PERMIT: 09110183 |
| | ADD: 1901 N FLAGLER DR |
| | CONT: LCI CONSTRUCTION |
| | TEL: (561)307-4951 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | DEC. 07/2009 |
| | |
| | 1) A1.1DETAIL# 03 AT THE TOP AND BOTTOM OF THE SHEET |
| | THE PLANS INDICATE STAIRS WITH A NOTE TO PROVIDE A NEW |
| | POWDER COAT HANDRAIL (SINGULAR) PLEASE REVIEW SECTION |
| | 1009.10., REQUIRED ON BOTH SIDES OF THE STAIRS, THEY DO |
| | NOT MEET ANY OF THE EXCEPTIONS. PLANS DO NOT HAVE |
| | DETAILS PLEASE ALSO REVIEW SECTION 1012.5, REQUIRED |
| | HANDRAIL EXTENSIONS. |
| | |
| | 2) A1.1 DETAIL# 3 SAME DETAIL THE BOTTOM SET OF STAIRS |
| | INDICATES THE USE OF A NEW CURTAIN THAT WILL HIDE THE |
| | STAIRS, ALTHOUGH IT IS NOT A DOOR THE CURTAIN STILL |
| | WILL BLOCK YOUR VIEW AS A DOOR WOULD PLEASE REVIEW |
| | SECTION 1008.1.5 FOR BOTH THE STAIR CONDITIONS. |
| | |
| | 3) SHEET A1.1 AND SHEET A5.1DETAIL# 2 INDICATES NEW |
| | TRAVERTINE TO BE LAMINATED TO THE TOP OF THE EXISTING |
| | STAIRS AND THE FLOOR FINISH TO REMAIN AS IS ON THE |
| | EXISTING STAGE, PLEASE PROVIDE THE RISER OF EACH OF THE |
| | STEPS AND REVIEW SECTION 1009.3 DIMENSIONAL UNIFORMITY, |
| | THE RISERS SHALL DEVIATE NO MORE THAN 0.375 OF AN INCH. |
| | |
| | 4A) SHEET A5.1 INDICATES THE USE OF ARMSTRONG |
| | SERPENTINA CURVED CLOUD SYSTEM, PLEASE PROVIDE THE |
| | MANUFACTURER???S SPECIFICATIONS. ADDITIONAL INFORMATION |
| | IS REQUIRED 106.1.2. FOR THE INSTALLATION OF CEILING |
| | TILE. 803.9.1.1. |
| | |
| | 4B) ARMSTRONG SERPENTINA CURVED CLOUD SYSTEM: 803.9.1 |
| | MATERIALS AND INSTALLATION. ACOUSTICAL MATERIALS |
| | COMPLYING WITH THE INTERIOR FINISH REQUIREMENTS OF |
| | SECTION 803 SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER'S RECOMMENDATIONS AND APPLICABLE |
| | PROVISIONS FOR APPLYING INTERIOR FINISH. |
| | |
| | |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |