| 2010-01-14 14:12:29 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE |
| | DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT |
| | IF FEES ARE DUE (REPEAT COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | 2- SHEET A-1: A) OPENING HEIGHT SHOWN ON THE ELEVATIONS |
| | FOR BEDROOM EGRESS WINDOWS DON'T CORRESPOND TO THE SIZE |
| | OF WINDOW SHOWN UNDERNEATH THE WINDOW. SH26 WINDOW |
| | DOESN'T HAVE 4'-3" HEIGHT. REVISE AS REQUIRED AND |
| | COORDINATE WITH ITEM #3(A) BELOW. |
| | |
| | B) SHOW EGRESS WINDOW FOR EXISTING BEDROOM. COORDINATE |
| | WITH ITEM #3(B) BELOW. |
| | |
| | 3- SHEET A-2: A) SH24 WINDOWS SPECIFIED FOR THE |
| | BEDROOMS DON'T COMPLY WITH THE MINIMUM OPENING HEIGHT |
| | REQUIRED FOR EGRESS. NEED TO COMPLY WITH SEC. R310.1.2 |
| | OF 2007 FLORIDA RESIDENTIAL CODE. REVISE AS REQUIRED |
| | (REPEAT COMMENT, NOT ADDRESSED AT ALL). |
| | |
| | B) EXISTING BEDROOM THAT IS ADJACENT TO NEW BEDROOM |
| | ADDITION HAVE NOT MEANS OF EGRESS. NEED TO PROVIDE |
| | MEANS OF EGRESS AS REQUIRED BY SEC. R310 OF 2007 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 4- SHEET S-1: A) SPECIFY HOW LONG (HOW MUCH EMBEDMENT) |
| | IS REQUIRED FOR THE ANCHOR BOLTS AT THE BOTTOM PLATE OF |
| | ALUMINUM COLUMNS TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | B) COORDINATE CONNECTORS SPECIFIED ON ROOF FRAMING PLAN |
| | AND SECTIONS AA AND BB ON SHEET D-1. CONNECTORS |
| | SPECIFIED DON'T MATCH AND MAKE SURE CORRECT CONNECTORS |
| | ARE USED. EX: WOOD TO WOOD CONNECTORS AND WOOD TO |
| | MASONRY CONNECTORS (REPEAT COMMENT). |
| | |
| | C) CLARIFY CONNECTORS SPECIFIED ON THE NEW BEDROOM/TV |
| | ROOM ADDITION ROOF FRAMING PLAN AREA. A2 CONNECTOR IS |
| | SHOWN TO ATTACH WOOD TRUSS TO WOOD TRUSS GIRDER. REVISE |
| | AS REQUIRED (REPEAT COMMENT). |
| | |
| | 5- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) WINDOW MULLIONS AS SHOWN ON ELEVATIONS (REPEAT |
| | COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | B) GLASS BLOCK AS SHOWN ON ELEVATIONS (REPEAT COMMENT. |
| | NOT ADDRESSED AT ALL). |
| | |
| | C) SLIDING GLASS DOORS (REPEAT COMMENT. NOT ADDRESSED |
| | AT ALL). |
| | |
| | D) PRECAST LINTELS AS SPECIFIED ON PLANS (REPEAT |
| | COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | E) ROOF SHINGLES (REPEAT COMMENT. NOT ADDRESSED AT |
| | ALL). |
| | |
| | F) FLAT ROOF (FOR NEW 1/2:12 PITCH ROOF). AND CLEARLY |
| | MARK ON THE PRODUCT APPROVAL THE FOLLOWING INFORMATION: |
| | * WHICH APPROVED ASSEMBLY IS GOING TO BE USED AND WHICH |
| | BASE SHEET FASTENING OPTION IS GOING TO BE USED. IF |
| | SELECTED ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7, |
| | THEN RAS 117 CALCULATIONS ARE REQUIRED FOR NAIL |
| | ENHANCING AT PERIMETER AND CORNER AREAS. CHECK GENERAL |
| | LIMITATION #7 ON LAST PAGE OF PRODUCT APPROVAL TO SEE |
| | IF RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED. |
| | **NOTE: SELECTED ASSEMBLY LIMITED BY GENERAL LIMITATION |
| | #9 CAN'T BE USED IN THIS BUILDING BECAUSE IT DOESN'T |
| | MEET THE DESIGN PRESSURES (REPEAT COMMENT. NOT |
| | ADDRESSED AT ALL). |
| | |
| | G) SPECIFY WHICH UNDERLAYMENT FROM NOA 07-1025.10 |
| | SUBMITTED IS GOING TO BE USED TO VERIFY COMPLIANCE WITH |
| | THE PRODUCT APPROVAL LIMITATIONS ON SHEET 4 OF 6. |
| | ***NOTE: TU PLUS IS DESIGNED FOR TILE UNDERLAYMENT NO |
| | SHINGLES (REPEAT COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | 6- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC (REPEAT |
| | COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | 7- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4 |
| | OF 2007 FLORIDA RESIDENTIAL CODE TO VERIFY THE 2500PSF |
| | SOIL BEARING CAPACITY REQUIRED BY THE ARCHITECT ON |
| | SHEET D-1 (REPEAT COMMENT. NOT ADDRESSED AT ALL). |
| | |
| | 8- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| | |
| | 9- REVISE THE ENERGY CALCULATIONS: A) NEED TO PROVIDE |
| | WINDOWS SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC |
| | FACTOR SHOWN ON ITEM #7 OR USE THE DEFAULT FACTORS |
| | SHOWN ON TABLE B2.1.1 OF CHAPTER 11 OF 2007 FLORIDA |
| | RESIDENTIAL CODE (REPEAT COMMENT. NOT ADDRESSED AT |
| | ALL). |
| | |
| | B) PERSON DOING THE CALCULATIONS TO REVIEW PLANS FOR |
| | COOLING AND HEATING INFORMATION (ITEMS #11, #12 AND |
| | #13). INFORMATION TO MATCH PLANS (REPEAT COMMENT). |
| | |
| | C) IF TAKING THE CEILING FAN CREDIT, THEN NEED TO |
| | SPECIFY CEILING FAN SIZES TO VERIFY COMPLIANCE WITH |
| | TABLE C4.2.1.1 OF 2007 FLORIDA RESIDENTIAL CODE, |
| | CHAPTER 11. |
| | |
| | D) COMPLETE ALL THE INFORMATION ON TOP OF THE FORM |
| | INCLUDING THE BUILDER'S NAME (REPEAT COMMENT). |
| | |
| | E) ROOF INFORMATION ON SHEET 2 OF 5 NEED TO BE REVISED. |
| | NEED TO ADD THE TYPE OF ROOF ON THE FLAT ROOF (REPEAT |
| | COMMENT, NOT ADDRESSED AT ALL). AND, THERE IS NOT |
| | BARREL TYPE ROOFING. SEE PLANS AND REVISE AS REQUIRED. |
| | |
| | 10- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $860.30 |
| | FOR UPDATED PERMIT VALUATION AND RADON FEES. |
| | |
| | 11- NEED TO PROVIDE CARBON MONOXIDE ALARM AS REQUIRED |
| | BY SEC. R313.4 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 12- NEW ADDITION NEED TO HAVE EGRESS DOOR TO COMPLY |
| | WITH SEC. R311.4 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |