2009-11-30 09:02:39DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. SHT S-1 THE SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE FLOOR PLAN SHOWS TWO
 NEW BATHROOMS AND A SINK IN THE T.V. ROOM WHEREAS THE
 RISER DIAGRAM ONLY SHOWS ONE BATHROOM AND DOES NOT SHOW
 THE SINK IN THE T.V. ROOM. SECTION 106.3.5.4(9).
  
 2. "INFORMATIONAL" THE SINK IN THE T.V. ROOM SHALL NOT
 DRAIN THROUGH THE WET VENT FOR THE BATHROOM GROUP.
 SECTION 909.1. ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUP SHALL CONNECT TO THE HORIZONTAL WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT.
  
 3. "INFORMATIONAL" IN THE INSTALLATION OR REMOVAL OF
 ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5. WHEN THE EXISTING KITCHEN
 AND EXISTING BATHROOM ARE BEING REMOVED, ABANDONED
 SANITARY LINES SHALL BE CAPPED OFF WITHIN 2 FEET OF
 ACTIVE LINES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  