Plan Review Notes
Plan Review Notes For Permit 09110178
Permit Number 09110178
Review Stop E
Sequence Number 1
Notes
Date Text
2009-12-01 13:01:27THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} DEPENDING ON THE METER LOCATION, A DISCONNECT MAY BE
 REQUIRED PER 230.70, 225.32. INDICATE LOCATION ON PLAN
 PER 230.72(A)(1) INDICATE IF THE ELECTRICAL SERVICE
 SHOWN ON THE PLAN IS NEW OR EXISTING.
  
 2} INDICATE THE CONDUCTOR SIZES FROM THE METER TO THE
 PANEL ON THE RISER DIAGRAM.
  
 3} THE RECEPTACLES THAT ARE TO BE REMOVED IN THE
 EXISTING LIVING ROOM AND FAMILY ROOM MUST BE
 REINSTALLED AND COMPLY WITH 210.52(A) (1).
  
 4} R313.2.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN.
 LOCATE SAME ON PLANS.
  
 5} THE ELECTRICAL SPECS, NOTE #1 REFERENCES THE 2005
 NEC. THE 2008 NEC WAS ADOPTED 10/1/09, PLEASE CHANGE
 ALL NOTES TO REFLECT THIS CHANGE.
  
 THE OWNER NAME IN THE TITLE BLOCK DOES NOT CORRELATE
 WITH THE NAME ON THE APPLICATION, CORRECT SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  