| 2009-12-08 12:00:03 | 2007 FBC W/2009 REVISIONS |
| | NEW SFR |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD FOR THE COMPONENTS AND CLADDING AS REQUIRED |
| | BY DCA RULE 9B-72 AND CITY AMENDMENTS. |
| | |
| | 2) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED |
| | BY FBC CHAPTER 13. |
| | |
| | 3) SUBMIT TWO COPIES OF A PROPERTY SURVEY. |
| | |
| | 4) SHOW ON THE SITE PLAN A-1 THAT THE SURFACE DRAINAGE |
| | REQUIREMENTS OF FBC R401.3 WILL BE MET AND THAT THE |
| | SURFACE WATER WILL BE DIRECTED TO APPROVED COLLECTIONS |
| | POINTS AND NOT ONTO ADJACENT PROPERTIES. |
| | |
| | 5) PLEASE UPDATE THE REFERENCES ON A-1 TO ACI 530, ACI |
| | 530.1, ACI 318 AND ACI 301 TO THE 2005 EDITIONS AS THE |
| | STANDARDS SPECIFIED IN CHAPTER 43 OF THE 2007 FBC |
| | RESIDENTIAL. |
| | |
| | 6) PLEASE UPDATE THE STAIR NOTES ON SHEET A-11 FROM |
| | 2004 TO THE 2007 FBCR. REVISE NOTE #1 TO R311.5.3.1. |
| | |
| | 7) REVISE THE GUARDRAIL NOTE 1 ON A-11 FROM NOT LESS |
| | THAN 42" TO NOT LESS THAN 34" WHEN MEASURED VERTICALLY |
| | FROM THE TREAD NOSINGS PER FBC R312.1. |
| | |
| | 8) THE LIVE LOAD NOTES FOR THE GUARDRAILS AND HANDRAILS |
| | IN THE CHART ON A-11 WERE NOT GIVEN. SEE TABLE R301.5 |
| | |
| | 9) ON A-10 THE DRAFT STOPPING NOTE CODE SECTION IS FROM |
| | THE 2004 HVHZ. PLEASE REVISE TO THE 2007 FBC R602.1.2 |
| | WHICH REQUIRES FIREBLOCKING AT THE TOP AND BOTTOM OF |
| | STAIR RUNS. |
| | |
| | 10) SPECIFY THE LOCATIONS AND MATERIAL THAT WILL BE |
| | USED FOR THE DRAFTSTOPPING AT THE FLOOR/CEILING |
| | ASSEMBLY THAT WILL SEPARATE IT INTO AREAS LESS THAN |
| | 1000 SQFT AS REQUIRED BY FBC R502.1.2. |
| | |
| | 11) SUBMIT THE SPECIFICATIONS AND LISTING FOR THE BBQ |
| | AND HOOD LOCATED ON THE LANAI OR INDICATE THAT THEY |
| | WILL BE APPLIED FOR UNDER A SEPARATE PERMIT. |
| | |
| | 12) SPECIFY CEILING MATERIAL THAT WILL BE INSTALLED IN |
| | THE LANAI AND THE COVERED PORCH ABOVE IT. |
| | |
| | 13) SHOW COMPLIANCE WITH FBC R309.2 FOR GARAGE |
| | SEPARATION. 5/8" TYPE X GYPSUM BOARD IS REQUIRED |
| | BETWEEN GARAGES AND HABITABLE ROOMS ABOVE. |
| | |
| | 14) ON A-10 THE BUILDING CROSS SECTION SHOWS A CONCRETE |
| | FLOOR AT THE COVERED PORCH ABOVE THE LANAI. SHEET S-2 |
| | AND 1 ON SD3 SHOWS WOOD TRUSSES. PLEASE CLARIFY. |
| | |
| | 15) ON SHEET S-2 THE FRONT BALCONY IS NOT SHOWN ON THE |
| | FLOOR PLAN. PROVIDE STRUCTURAL DETAILS AND DIMENSIONS |
| | FOR THIS CONCRETE BALCONY. |
| | |
| | 16) ON SHEET S-3 REVISE THE ROOF SHEATHING FASTENING TO |
| | 8D RING SHANK NAILS TO CORRESPOND WITH SHEET SD1 AND |
| | FBC R803.2.3.1. |
| | |
| | 17) ON SHEET S-3 UPDATE THE WIND LOAD TABLE TO |
| | REFERENCE ASCE 7-05 AS SPECIFIED IN FBC R CHAPTER 43. |
| | |
| | 18) PLEASE CORRECT DETAIL 10 ON SD2 WHICH HAS THE TITLE |
| | ON TOP OF THE NOTES. |
| | |
| | 19) THE H-35 SINGLE HUNG WINDOWS SPECIFIED AT TWO OF |
| | THE SECOND FLOOR BEDROOMS, DO NOT HAVE THE REQUIRED 5.7 |
| | SQFT MINIMUM NET CLEAR OPENING REQUIRED BY FBC R310.1.1 |
| | FOR EMERGENCY ESCAPE AND RESCUE OPENINGS. (WINDOWS R-1 |
| | THRU R-4 AND S-1) |
| | |
| | 20) ON S-2 THE TRUSS IDS IN THE CONNECTOR SCHEDULE ARE |
| | LISTED WITHOUT THE "0" BETWEEN THE NUMBERS THAT THE |
| | FRAMING PLAN LISTS. FOR EXAMPLE THE FRAMING PLAN LISTS |
| | S01 AND THE SCHEDULE HAS S1. IN ORDER TO AVOID |
| | CONFUSION, PLEASE COORDINATE THE ID TAGS. |
| | |
| | 21) ON SHEETS S-1 THE FOUNDATION PLAN AND S-2 THE FLOOR |
| | FRAMING PLAN THE COLUMN AT THE LANAI THAT SUPPORTS THE |
| | BEAMS B111 AND B112 ARE NOT SPECIFIED. PLEASE PROVIDE |
| | DETAILS FOR THIS COLUMN. |
| | |
| | 22) PLEASE SPECIFY THE DESIGN PRESSURES FOR THE |
| | EXTERIOR DOORS AND WINDOWS IN THE SCHEDULE ON SHEET |
| | A-11. FBC R301.2.1 |
| | |
| | 23) PLEASE PROVIDE A WRITTEN RESPONSE TO THE COMMENTS |
| | INDICATING HOW THEY HAVE BEEN ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |