| 2011-01-31 12:27:27 | BUILDING PLAN REVIEW |
| | PERMIT: 09110104 |
| | ADD: 1320 N TAMARIND AVE |
| | CONT: GENERAL ENGINEERING DEVELOPMENT & CONSTRUCTION |
| | CORP. CGC1508383/ CCC1328731 |
| | TEL: (561)509-4000 |
| | DEC.27/2010 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) PLANS RESUBMITTED WITH WINDOW WITHIN 10 FEET OF THE |
| | EXTERIOR STAIR NEED TO BE 1 HOUR FIRE RATED . PRODUCT |
| | APPROVAL FOR THE FIRE RATING WAS SUBMITTED BUT NO |
| | PRODUCT REPORTS WERE SUBMITTED FOR THE REQUIRED STORM |
| | SHUTTER. FIRE RATED GLASS WINDOWS DO NOT MEET THE LARGE |
| | MISSILE TESTING REQUIREMING THE WINDOW TO BE STORM |
| | SHUTTERED IN THE CASE OF A HIGH WIND EVENT. PROVIDE |
| | BEFORE INSPECTION |
| | 2007/ 2009 FBC-B 1023.6 EXTERIOR RAMPS AND STAIRWAY |
| | PROTECTION. EXTERIOR EXIT RAMPS AND STAIRWAYS SHALL BE |
| | SEPARATED FROM THE INTERIOR OF THE BUILDING AS REQUIRED |
| | IN SECTION 1020.1. OPENINGS SHALL BE LIMITED TO THOSE |
| | NECESSARY FOR EGRESS FROM NORMALLY OCCUPIED SPACES. |
| | 1020.1.1 OPENINGS AND PENETRATIONS. EXIT ENCLOSURE |
| | OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF SECTION 715. |
| | 2007/2009 FBC-B TABLE 715.4. |
| | |
| | 2)THE SUBMITTED ROOFING REPORT MIAMI-DADE NOA |
| | 07-822.10: |
| | 2A) DOES NOT HAVE ANY OF THE SUB-SYSTEMS HIGHLIGHTED AS |
| | TO WHICH SYSTEM WILL BE INSTALLED. |
| | 2B) PLEASE INDICATE WHICH OF THE INSULATED SYSTEMS WILL |
| | BE INSTALLED, NOTE MOST CASES SEE LIMITATION# 7 OCCURS |
| | AND ENHANCED FASTENING WILL BE REQUIRED FOR ZONES 2 & |
| | 3. |
| | RAS 117 CALCULATIONS ARE TO BE PREPARED BY EITHER A |
| | FLORIDA P.E. OR REGISTERED ARCHITECT. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |