| Plan Review Notes For Permit 09110104 |
| Permit Number |
09110104 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-12-22 14:00:59 | FBC PLUMBING 2007 REVIEW #2 | | | DENIED: | | | | | | 1. SANITARY RISER DIAGRAM SHOWS WATER CLOSETS ON THE | | | 2ND FLOOR WITH HORIZONTAL DRY VENTS. | | | PLUMBING 905.4 VERTICAL RISE OF VENT. EVERY DRY VENT | | | SHALL RISE VERTICALLY TO A MINIMUM OF 6 INCHES (152 MM) | | | ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST TRAP OR | | | TRAPPED FIXTURE BEING VENTED. | | | | | | 2. SANITARY RISER DIAGRAM SHOWS A KITCHEN SINK WET | | | VENTING A TUB. | | | PLUMBING 909.1 HORIZONTAL WET VENT PERMITTED. ONLY THE | | | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO | | | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL | | | WET VENT. | | | | | | 3. BY MOVING THE LOCATION OF THE 2ND FLOOR BATHROOMS, A | | | WATER DISTRIBUTION DRAWING AND WATER HEATER DETAIL WILL | | | BE REQUIRED. | | | FBC 106.3.5.1.3 (3) & (5) PLUMBING |
|