Plan Review Notes
Plan Review Notes For Permit 09110104
Permit Number 09110104
Review Stop P
Sequence Number 2
Notes
Date Text
2010-12-22 14:00:59FBC PLUMBING 2007 REVIEW #2
 DENIED:
  
 1. SANITARY RISER DIAGRAM SHOWS WATER CLOSETS ON THE
 2ND FLOOR WITH HORIZONTAL DRY VENTS.
 PLUMBING 905.4 VERTICAL RISE OF VENT. EVERY DRY VENT
 SHALL RISE VERTICALLY TO A MINIMUM OF 6 INCHES (152 MM)
 ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST TRAP OR
 TRAPPED FIXTURE BEING VENTED.
  
 2. SANITARY RISER DIAGRAM SHOWS A KITCHEN SINK WET
 VENTING A TUB.
 PLUMBING 909.1 HORIZONTAL WET VENT PERMITTED. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 3. BY MOVING THE LOCATION OF THE 2ND FLOOR BATHROOMS, A
 WATER DISTRIBUTION DRAWING AND WATER HEATER DETAIL WILL
 BE REQUIRED.
 FBC 106.3.5.1.3 (3) & (5) PLUMBING