2010-12-01 13:58:511320 NORTH TAMARIND AVENUE
 REPAIR FIRE DAMAGE IN FIRST FLOOR AND SECOND FLOOR
 PERMIT NUMBER 09110104
  
  
 1. THIS OFFICE HAS REVIEWED THE REVISED PLANS AND HAVE
 ACKNOWLEDGED THE REVISIONS TO THE DRAWINGS REGARDING
 THE PREVIOUS FIRE CODE COMMENTS.
  
 2. THE UPSTAIRS PORTION OF THE BUILDING SHALL COMPLY
 WITH NFPA 101 CHAPTER 26, LODGING OR ROOMING HOUSES.
 SINCE THE FIRE IT IS BELIEVED THAT THE ROOMING HOUSE
 PORTION HAS BEEN CLOSED. ACCORDING TO THE PREVAILING
 FIRE CODE, THE REQUIREMENTS OF CHAPTER 26 "SHALL APPLY
 TO NEW BUILDINGS OR MODIFIED BUILDINGS ACCORDING TO THE
 PROVISIONS OF 1.3.1 OF THIS CODE". SECTION 1.3.1
 INDICATES " THE CODE SHALL APPLY TO BOTH NEW
 CONSTRUCTION AND EXISTING BUILDINGS AND EXISTING
 STRUCTURES.
  
 3. NFPA 101 CHAPTER 26, LODGING OR ROOMING HOUSES
 SPECIFICALLY 26.3.6.1 "ALL NEW LODGING OR ROOMING
 HOUSES, OTHER THAN THOSE MEETING 26.3.6.2 SHALL BE
 PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH 26.3.6.3. SINCE THE ROOMING
 HOUSE WAS CLOSED FOR A LONG PERIOD OF TIME, THAT
 PORTION IS BEING CONSIDERED NEW. IT DOES NOT APPEAR
 THAT THE BUILDING MEETS THE EXCEPTION FOR NO SPRINKLERS
 AND THEREFORE THE BUILDING WILL NEED TO BE FIRE
 SPRINKLER PROTECTED WITH A MINIMUM OF AT LEAST A 13R
 FIRE SPRINKLER SYSTEM. SEPARATE PLANS AND PERMITS ARE
 REQUIRED PRIOR TO INSTALLATION.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM.
  
 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
  
 THE PERMIT IS APPROVED PROVISO WITH THE UNDERSTANDING
 THAT THE ROOMING HOUSE PORTION BE FIRE SPRINKLER
 PROTECTED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION