2010-03-15 17:07:21BUILDING PLAN REVIEW
 PERMIT: 09110104
 ADD: 1320 N TAMARIND AVE
 CONT: GENERAL ENGINEERING DEVELOPMENT & CONSTRUCTION
 CORP
 TEL: (561)509-4000
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET 5 DETAIL A INDICATES A ROOF FRAMING SECTION
 WITH NEW 2X8 RAFTERS @ 12 INCHES ON CENTER, PLANS FAIL
 TO PROVIDE THE SPECIES OF WOOD AND GRADE OF WOOD,
 PLEASE PROVIDE
 FOR COMPLIANCE WITH TABLE 2308.10.3.1.
  
 2) SHEET 5 DETAIL A ALSO INDICATES A WOOD BEAM (2) 2X8S
 THE PLANS ARE NOT CLEAR IF A SINGLE 2X8 IS BEING ADDED
 TO AN EXISTING 2X8 BEAM OR IF THE (2) 2X8S MAKE UP THE
 TOTAL BEAM.
 106.1.2 ADDITIONAL INFORMATION REQUIRED. IT APPEARS
 THAT AGAIN NOT ENOUGH INFORMATION HAS BEEN PROVIDED.
 SPECIES OF WOOD, GRADE OF WOOD, FB VALUE, AND THE SPAN
 ON THE OTHER SIDE OF THE NEW WOOD BEAM, IT APPEARS
 THERE ARE EXISTING 2X6S @ 24 INCHES ON CENTER. IT
 APPEARS THIS BEAM IS LIGHT. PLEASE PROVIDE THE BEAM
 CALCULATIONS FOR A SIMPLE SPAN CONFIGURATION.WOOD
 STRUCTURAL DESIGN DATA 1992 REVISIONS WOOD BEAMS SAFE
 LOAD TABLES SPANS OF 15'-0". 2308.4.2 STRUCTURAL
 ELEMENTS OR NOT DESSCRIBED WITHIN.
  
 3) SHEET 5 DETAIL A INDICATE A BUILT UP WOOD BEAM BUT
 DO NOT PROVIDE AS TO WHAT CONNECTIONS, UPLIFT, LATERAL
 AND GRAVITY LOADS WILL BE ACTING ON THIS BEAM NOR THE
 TIE DOWN SYSTEM,
 MWFRS MAIN WIND FORCE RESISTING SYSTEM. WHAT TRANSFERS
 THE GRAVITY LOADS INTO TTHE STRUCTURE AND TIE TO THE
 FOUNDATION BELOW. FBC-B 1609.1.1.
  
 4A) SHEET 1 IS NOT CLEAR AS TO THE HORIZONTAL OCCUPANCY
 SEPERATION THAT IS REQUIRED BETWEEN THE
 BUSINESSOCCUPANCY AND R2 ON THE SECOND FLOOR. TWO HOUR
 HORIZONTAL OCCUPNCY SEPERATION WILL BE REQUIRED PLEASE
 REVIEW SECTION FBC-B 711.3 FIRE- RESISTANCE RATING. THE
 FIRE-RESISTANCE RATING OF FLOOR AND ROOF ASSEMBLIES
 SHALL NOT BE LESS THAN THAT REQUIRED BY THE BUILDING
 TYPE OF CONSTRUCTION. WHERE THE FLOOR ASSEMBLY
 SEPARATES MIXED OCCUPANCIES, THE ASSEMBLY SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN THAT REQUIRED
 BY SECTION 508.3.3 BASED ON THE OCCUPANCIES BEING
 SEPARATED. TABLE 508.3.3 BUSINESS/ R2, UNSPRINKLERED:
 2HOURS. PLEASE PROVIDE UL OR OTHER LISTED ASSEMBLY.
  
 4B) THE TENANT SEPERATION WALL THAT SEPERATES TENANT 1
 AND TENANT 2 APPEARS TO BE A BEARING WALL, 2ND FLOOR
 FLOOR JOIST, AND WILL ALSO BE REQUIRED TO BE A 2 HOUR
 WALL SINCE IT SUPPORTS THE 2 HR RATED FLOOR CEILING
 ASSEMBLY. PLEASE PROVIDE A UL LISTED ASSEMBLY OR
 EQUIVALENT.
  
 5) PLEASE ALSO REVIEW REQUIRED SEPERATION FOR EACH OF
 THE R2 TENANCIES. 711.3 FIRE-RESISTANCE RATING. FLOOR
 ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME
 BUILDING OR SLEEPING UNITS IN OCCUPANCIES IN GROUP R-1,
 HOTEL OCCUPANCIES, R-2 AND I-1; AND FLOOR ASSEMBLIES
 SEPARATING INDIVIDUAL TENANT SPACES IN THE SAME
 BUILDING IN ALL OTHER OCCUPANCIES SHALL BE A MINIMUM OF
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION.
  
 6) PLEASE REVIEW DRAFT STOPPING REQUIREMENTS:BUILDING
 PROVISO: IF THE CONTRACTORS DO NOT REMOVE CEILING
 ASSEMBLIES AND OR FLOOR /CEILING ASSEMBLIES THEN THE
 DRAFT STOPPING REQUIREMENTS WILL NOT BE REQUIRED.
 5-11-2010 J. W.
 717.3.2 GROUPS R-1, R-2, R-3 AND R-4. DRAFTSTOPPING
 SHALL BE PROVIDED IN FLOOR/CEILING SPACES IN GROUP R-1
 BUILDINGS, IN GROUP R-2 BUILDINGS WITH THREE OR MORE
 DWELLING UNITS, IN GROUP R-3 BUILDINGS WITH TWO
 DWELLING UNITS AND IN GROUP R-4 BUILDINGS.
 DRAFTSTOPPING SHALL BE LOCATED ABOVE AND IN LINE WITH
 THE DWELLING UNIT AND SLEEPING UNIT SEPARATIONS.
  
 717.4 DRAFTSTOPPING IN ATTICS. IN COMBUSTIBLE
 CONSTRUCTION, DRAFTSTOPPING SHALL BE INSTALLED TO
 SUBDIVIDE ATTIC SPACES AND CONCEALED ROOF SPACES IN THE
 LOCATIONS PRESCRIBED IN SECTIONS 717.4.2 AND 717.4.3.
 VENTILATION OF CONCEALED ROOF SPACES SHALL BE
 MAINTAINED IN ACCORDANCE WITH SECTION 1203.2.
  
 717.4.2 GROUPS R-1 AND R-2. DRAFTSTOPPING SHALL BE
 PROVIDED IN ATTICS, MANSARDS, OVERHANGS OR OTHER
 CONCEALED ROOF SPACES OF GROUP R-2 BUILDINGS WITH THREE
 OR MORE DWELLING UNITS AND IN ALL GROUP R-1 BUILDINGS.
 DRAFTSTOPPING SHALL BE INSTALLED ABOVE, AND IN LINE
 WITH, SLEEPING UNIT AND DWELLING UNIT SEPARATION WALLS
 THAT DO NOT EXTEND TO THE UNDERSIDE OF THE ROOF
 SHEATHING ABOVE.
 EXCEPTIONS:
 1. WHERE CORRIDOR WALLS PROVIDE A SLEEPING UNIT OR
 DWELLING UNIT SEPARATION, DRAFTSTOPPING SHALL ONLY BE
 REQUIRED ABOVE ONE OF THE CORRIDOR WALLS.
 2. DRAFTSTOPPING IS NOT REQUIRED IN BUILDINGS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1.
 3. IN OCCUPANCIES IN GROUP R-2 THAT DO NOT EXCEED FOUR
 STORIES IN HEIGHT, THE ATTIC SPACE SHALL BE SUBDIVIDED
 BY DRAFTSTOPS INTO AREAS NOT EXCEEDING 3,000 SQUARE
 FEET (279 M2) OR ABOVE EVERY TWO DWELLING UNITS,
 WHICHEVER IS SMALLER.
 4. DRAFTSTOPPING IS NOT REQUIRED IN BUILDINGS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.2, PROVIDED THAT
 AUTOMATIC SPRINKLERS ARE ALSO INSTALLED IN THE
 COMBUSTIBLE CONCEALED SPACES.
  
 7A) SUBMITTED IS A PRODUCT APPROVAL NOA 07-0214.05 FOR
 SERIES 100 STORM SAFE SINGLE HUNG WINDOW, THE PLANS DO
 NOT INDICATE THE 2ND FLOOR WINDOWS ARE TO BE REPLACED
 ONLY THE FIRSST FLOOR WINDOWS. IF THTE SECOND FLOOR
 WINDOWS ARE TO BE REPLACED PLEASE PROVIDE BY EITHER
 CIRLING THE UNIT TO BE INSTALLED, WINDOW HEIGHT AND
 WIDTH ON THE PRODUCT APPROVAL OR PROVIDE INFORMATION ON
 THE PLANS. PROVIDE THE OVERALL WINDOW DIMENSIONS TO BE
 INSTALLED, THE CLEAR VENT SIZE MUST BE 5.7 SQ FT.
  
 7B) THE SUBMITTED NOA 07-0214.05 HAS BEEN PREVIOUSLY
 STAMPED WITH A DIFFERENT PERMIT NUMBER PLEASE PROVIDE
 NEW SETS. RECORD RETENTION WILL NOT BE ABLE TO COPY AND
 BE LEGIBLE FOR RECORD RETENSION.
  
 8) THE SUBMITTED ROOFING REPORT MIAMI-DADE NOA
 07-822.10:
 8A) DOES NOT HAVE ANY OF TTTHE SUB-SYSTEMS HIGHLIGHTED
 AS TO WHICH SYSTEM WILL BE INSTALLED.
 8B) PLEASE INDICATE WHICH OF THE INSULATED SYSTEMS WILL
 BE INSTALLED, NOTE MOST CASES SEE LIMITATION# 7 OCCURS
 AND ENHANCED FASTENING WILL BE REQUIRED FOR ZONES 2 &
 3.
 RAS 117 CALCULATIONS ARE TO BE PREPARED BY EITHER A
 FLORIDA P.E. OR REGISTERED ARCHITECT.
 8C) PLEASE NOTE SHEET ROOFING DETAIL INDICATES THE NEW
 ROOF DECKING TO BE 15/32 CDX PLYWOOD WHERE AS THE
 SUBMITTED NOA REQUIRES A MINIMUM OF 19/32 CDX PLYWOOD.
  
 9) SHEET# 4 SOUTH ELEVATION PLEASE REVIEW 1023.6
 EXCEPTION# 1 3/4 HR OPENING PROTECTION FOR WINDOWS
 LOCATED WITHIN 10'-0" OF EXTERIOR STAIRS.
  
 10) EXISTING BUILDING CODE 705.5.1 CORRIDOR DOORS.
 CORRIDOR DOORS IN THE WORK AREA SHALL NOT BE
 CONSTRUCTED OF HOLLOW CORE WOOD AND SHALL NOT CONTAIN
 LOUVERS. ALL DWELLING UNIT OR SLEEPING UNIT CORRIDOR
 DOORS IN WORK AREAS IN BUILDINGS OF GROUPS R-1, R-2,
 AND I-1 SHALL BE AT LEAST 13/8-INCH (35 MM) SOLID CORE
 WOOD OR APPROVED EQUIVALENT AND SHALL NOT HAVE ANY
 GLASS PANELS, OTHER THAN APPROVED WIRED GLASS OR OTHER
 APPROVED GLAZING MATERIAL IN METAL FRAMES. ALL DWELLING
 UNIT OR SLEEPING UNIT CORRIDOR DOORS IN WORK AREAS IN
 BUILDINGS OF GROUPS R-1, R-2, AND I-1 SHALL BE EQUIPPED
 WITH APPROVED DOOR CLOSERS. ALL REPLACEMENT DOORS SHALL
 BE 13/4-INCH (45 MM) SOLID BONDED WOOD CORE OR APPROVED
 EQUIVALENT, UNLESS THE EXISTING FRAME WILL ACCOMMODATE
 ONLY A 13/8-INCH (35 MM) DOOR.
  
 11) THE PLANS ARE NOT CLEAR AS TO WHAT EXTENT THE 2ND
 FLOOR IS TO BE REMODELED, WILL THE DRRYWALL BE REMOVED
 FROM ALL WALLS, PLANS CURRENTLY DO NOT INDICATE ANY
 TYPE OF WALL OR CEILING INSULATION?
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved