| 2010-03-25 00:11:21 | *****DENIED***** |
| | |
| | |
| | 01. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 |
| | EDITION. |
| | |
| | 02. ON SHEET 4, POST THE NUMERICAL ADDRESS ON THE |
| | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS NORTH |
| | TAMARIND AVENUE. AS PER WEST PALM BEACH CODE, BUILDING |
| | ADDRESS NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND |
| | NO LESS THAN 1" IN WIDTH/STROKE. THE BUSINESS SUITE |
| | NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO LESS |
| | THAN 1" IN WIDTH/STROKE. |
| | |
| | 03. NO FIRE EXTINGUISHER SHOWN IN THE # 1 BUSINESS |
| | SUITE. |
| | |
| | 04. NO DOOR DESIGNATION/NUMBER FOR THE DOOR |
| | ENTERING/EXITING THE SECOND FLOOR LIVING ROOM. |
| | ******************************************************* |
| | ******************************************************* |
| | ******************************************************* |
| | THE REFERENCE FOR THE FOLLOWING COMMENTS ARE BASED ON |
| | CHAPTER 26 (LODGING OR ROOMING HOUSES) OF NFPA 101 - |
| | LIFE SAFETY CODE - 2006 EDITION |
| | ******************************************************* |
| | ******************************************************* |
| | ******************************************************* |
| | 05. SLEEPING ROOM DOORS WHICH WHICH OPEN INTO EXIT |
| | ACCESS CORRIDOR SHALL BE FIRE RATED, SELF CLOSING, AND |
| | LATCHES UPON RELEASE. AMEND TO REFLECT AS THUS IN THE |
| | DOOR SCHEDULE. |
| | |
| | 06. ON SHEET 2, SECOND FLOOR, NO MANUAL FIRE ALARM PULL |
| | STATIONS SHOWN IN THE NATURAL EXIT ACCESS PATH NEAR |
| | EACH REQUIRED EXIT FROM AN AREA. |
| | |
| | 07. ON SHEET 2, SECOND FLOOR, NO VISIBLE SIGNALS FOR |
| | THE HEARING IMPAIRED. THESE DEVICES SHALL NOT BE |
| | REQUIRED WHERE THE PROPRIETOR (OR PROPRIETOR'S AGENT) |
| | RESIDES IN THE BUILDING AND THERE ARE FIVE OR FEWER |
| | ROOMS FOR RENT. |
| | |
| | 08. EXISTING STAIRS SHALL BE PERMITTED TO REMAIN IN |
| | USE, PROVIDED THAT THEY MEET THE REQUIREMENTS FOR |
| | EXISTING STAIRS SHOWN IN TABLE 7.2.2.2.1.19(B) OF NFPA |
| | 101 - LIFE SAFETY CODE - 2006 EDITION. |
| | |
| | 09. STAIRS SHALL HAVE GUARDRAILS ON BOTH SIDES. |
| | |
| | 10. WHAT IS THE DISTANCE AND/OR FIRE RATING OPENING |
| | PROTECTION FOR THE WINDOWS, AS SHOWN ON SHEET #4, |
| | LOCATED NEAR THE EXTERIOR STAIRS ON THE SOUTH |
| | ELEVATION. |
| | |
| | 11. BASED ON INFORMATION GAINED FROM PLANNING AND |
| | ZONING DEPARTMENT, A FIRE SPRINKLER SYSTEM MAY BE |
| | REQUIRED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATINGWHERE/HOW EACH ITEM WAS ADDRESSED |
| | |
| | |