2010-03-25 00:11:21*****DENIED*****
  
  
 01. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 02. ON SHEET 4, POST THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS NORTH
 TAMARIND AVENUE. AS PER WEST PALM BEACH CODE, BUILDING
 ADDRESS NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND
 NO LESS THAN 1" IN WIDTH/STROKE. THE BUSINESS SUITE
 NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH/STROKE.
  
 03. NO FIRE EXTINGUISHER SHOWN IN THE # 1 BUSINESS
 SUITE.
  
 04. NO DOOR DESIGNATION/NUMBER FOR THE DOOR
 ENTERING/EXITING THE SECOND FLOOR LIVING ROOM.
 *******************************************************
 *******************************************************
 *******************************************************
 THE REFERENCE FOR THE FOLLOWING COMMENTS ARE BASED ON
 CHAPTER 26 (LODGING OR ROOMING HOUSES) OF NFPA 101 -
 LIFE SAFETY CODE - 2006 EDITION
 *******************************************************
 *******************************************************
 *******************************************************
 05. SLEEPING ROOM DOORS WHICH WHICH OPEN INTO EXIT
 ACCESS CORRIDOR SHALL BE FIRE RATED, SELF CLOSING, AND
 LATCHES UPON RELEASE. AMEND TO REFLECT AS THUS IN THE
 DOOR SCHEDULE.
  
 06. ON SHEET 2, SECOND FLOOR, NO MANUAL FIRE ALARM PULL
 STATIONS SHOWN IN THE NATURAL EXIT ACCESS PATH NEAR
 EACH REQUIRED EXIT FROM AN AREA.
  
 07. ON SHEET 2, SECOND FLOOR, NO VISIBLE SIGNALS FOR
 THE HEARING IMPAIRED. THESE DEVICES SHALL NOT BE
 REQUIRED WHERE THE PROPRIETOR (OR PROPRIETOR'S AGENT)
 RESIDES IN THE BUILDING AND THERE ARE FIVE OR FEWER
 ROOMS FOR RENT.
  
 08. EXISTING STAIRS SHALL BE PERMITTED TO REMAIN IN
 USE, PROVIDED THAT THEY MEET THE REQUIREMENTS FOR
 EXISTING STAIRS SHOWN IN TABLE 7.2.2.2.1.19(B) OF NFPA
 101 - LIFE SAFETY CODE - 2006 EDITION.
  
 09. STAIRS SHALL HAVE GUARDRAILS ON BOTH SIDES.
  
 10. WHAT IS THE DISTANCE AND/OR FIRE RATING OPENING
 PROTECTION FOR THE WINDOWS, AS SHOWN ON SHEET #4,
 LOCATED NEAR THE EXTERIOR STAIRS ON THE SOUTH
 ELEVATION.
  
 11. BASED ON INFORMATION GAINED FROM PLANNING AND
 ZONING DEPARTMENT, A FIRE SPRINKLER SYSTEM MAY BE
 REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATINGWHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
 OR
 BATTALION CHIEF MIKE CARSILLO
 FIRE MARSHAL - FIRE PREVENTION BUREAU
 561-804-4709