| 2009-11-18 13:46:01 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | FBC-2007 CHAPTER 11 |
| | |
| | 1. SHT 2 FLOOR PLAN. SHOW THE LOCATION OF THE REQUIRED |
| | DRINKING FOUNTAIN. TABLE 403.1. |
| | |
| | 2. SHT 2 DETAIL FOR THE TOILET ROOM INDICATES THE W/C |
| | TO BE 2'0" OFF THE WALL. FIGURE 28 SHOWS THE W/C TO BE |
| | 18" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. ALSO |
| | THE CLEAR FLOOR SPACE FOR THE W/C SHALL REFLECT THE |
| | REQUIREMENTS FOR THE CLEAR FLOOR SPACE IN FIGURE 28, |
| | NOT 30X48 INCHES AS INDICATED. |
| | |
| | 3. SHT 2 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | |
| | ___W/C: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | |
| | ___LAV: |
| | A. 11-4.19.2 CLEARANCE |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | |
| | 4. SHT 4 SANITARY RISER DIAGRAM. PER SECTIONS 905.3 & |
| | 905.4 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN |
| | SHALL CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL |
| | DRAIN LINE. - EVERY DRY VENT SHALL RISE VERTICALLY TO A |
| | MINIMUM OF 6 INCHES ABOVE THE FLOOD RIM LEVEL OF THE |
| | HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. THE VENT |
| | PAST THE TOILET ROOM DOES NOT MEET THESE CODE |
| | REQUIREMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |