| Plan Review Notes For Permit 09110083 |
| Permit Number |
09110083 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-01 19:44:56 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. A/C NOTE #12 CALLS FOR CONDENSATE TO DISCHARGE IN | | | MOP SINK. CONDENSATE SHALL NOT DISCHARGE INTO SANITARY | | | SEWER SYSTEM PER CITY ORDINANCE. CONDENSATE FROM THE | | | COOLING COIL SHALL BE CONVEYED FROM THE DRAIN PAN | | | OUTLET TO AN APPROVED PLACE OF DISPOSAL, SUCH AS | | | OUTDOORS AT A WATER PERMEABLE LOCATION, MIN. 12" FROM | | | BUILDING PER FBC-M 307.2.1. CONDENSATE SHALL NOT | | | DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO | | | CAUSE A NUISANCE. | | | | | | 2. SHOW SIZES OF RETURN AIR TRANSFER DUCTS ON PLAN TO | | | DEMONSTRATE COMPLAINCE WITH FBC-M 601.4 FOR BALANCED | | | RETURN AIR FLOW. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|