Text |
| 2009-11-30 16:02:12 | ** DENIED ** |
| | |
| | 1) NOTE: THE FOLLOWING CODES ARE REFLECTED ON COVER |
| | SHEET WHICH ARE NOT CURRENT ADOPTED CODES BASED ON |
| | PERMIT APPLICATION DATE. |
| | 2005 NFPA-70 (NEC) |
| | 2006 NFPA-72 |
| | |
| | SHOULD BE: |
| | 2008 NFPA70 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: LIGHTING CONTROLS FOR AUTOMATED SHUT OFF IS |
| | REQUIRED FOR NON-EXAM ROOMS. 13-415.AB.1.1,.1.2. |
| | LOCATIONS SUCH AS FILE STORAGE, PHONE/SERVER ROOM, NEW |
| | BATHROOM WOULD BE SUCH LOCATIONS. |
| | |
| | 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.AB.5 (13-415.B.2.2) |
| | |
| | 4) NOTE: PLEASE INDICATE NEW OR EXISTING GFI FOR |
| | CONDENSING UNIT. 230.63, 210.8B2 |
| | |
| | 5) NOTE: PLEASE KNOW THAT A REVISED PANEL SCHEDULE WILL |
| | BE REQUIRED FOR NEW CIRCUITS AND EXISTING. THESE ARE |
| | REQUIRED TO BE SPECIFIC TOR ROOMS AND AREAS IN WHICH |
| | THEY FEED. |
| | 408.4. |
| | |
| | 6) NOTE: PLEASE SEE MINIMUM CLEARANCES FROM BATH/SHOWER |
| | LOCATIONS. PLANS INDICATE AN ELECTRICAL WATER HEATER |
| | RIGHT NEXT TO THE SHOWER. IS THIS ACCURATE? |
| | PLEASE SEE 422.30,31 FOR REQUIRED DISCONNECT FOR |
| | ELECTRIC WATER HEATER. PLANS INDICATE A RECEPTACLE FOR |
| | CONNECTION WHICH IS NOT PERMITTED. |
| | |
| | 7) NOTE: IF BUILDING CONTAINS FIRE ALARM, PLEASE |
| | INDICATE HORN, STROBES, AND LEVELS FOR ADA PER FBC |
| | 11-4.28.1,.2 AND.3. |
| | |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |