| Plan Review Notes For Permit 09110018 |
| Permit Number |
09110018 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-11-06 10:19:21 | DENIED | | | REFERENCE: | | | FBC-2007 PLUMBING | | | CITY WPB MUNICIPAL CODES | | | FBC-2007 CHAPTER 11 | | | | | | 1. SHT A2.1 FLOOR PLAN SHOWS THE TOILET ROOM DOOR | | | SWINGING INTO THE CLEAR FLOOR SPACE OF THE DRINKING | | | FOUNTAIN. PER SECTION 11-4.22.2 DOORS SHALL NOT SWING | | | INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. | | | | | | 2. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY | | | DEPT. PLEASE CONTACT HOLLY MCGRATH, LABORATORY | | | SUPERVISOR @ (561) 822-2271, FAX (561) 822-2279 OR | | | E-MAIL [email protected]. ARTICLE III SECTION 90-124(7), | | | AND SECTIONS 1003.1 & 1003.3.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|