Plan Review Notes
Plan Review Notes For Permit 09110018
Permit Number 09110018
Review Stop M
Sequence Number 1
Notes
Date Text
2009-11-23 09:05:27REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. MOTORIZED DAMPER WITH SHUTOFF DAMPER CONTROLS IS
 REQUIRED ON THE OUTSIDE AIR INTAHE IN ACCORDANCE WITH
 FBC-B 13-409.AB.3.3.
  
 2. A TYPE 2 HOOD IS REQUIRED OVER THE OVEN IN
 ACCORDANCE WITH FBC-M 507.2.2. THIS HOOD SHOULD MAY BE
 COVERED UNDER A SEPARATE PERMIT IN CONJUNCTION WITH THE
 TYPE 1 HOOD.
  
 3. PRODUCT APPROVAL IS REQUIRED FOR ROOFTOP
 PRE-ENGINEERED A/C STAND IN ACCORDANCE WITH FBC-B
 106.3.3 AND FAC RULE 9B-72. IF THE PROPOSED STAND IS
 FOR WALK-IN REMOTE CONDENSERS, THE PRODUCT APPROVAL MAY
 BE SUBMITTED WITH THE SEPARATE PERMIT APPLICATION FOR
 THE WALK-IN COOLERS.
  
 NOTE: NEW ROOFTOP CONDENSERS SHALL MEET THE
 REQUIREMENTS FOR GUARDS IF WITHIN 10' OF THE ROOF EDGE
 PER FBC-M 304.10 AND FOR SERVICE ACCESS IN ACCORDANCE
 WITH FBC-M 306.5.
  
 ENERGY CALCULATIONS:
  
 4. A LARGE PORTION OF THIS BUILDING IS BEING CONVERTED
 FROM UNCONDITIONED TO CONDITIONED SPACE. PER ENERGY
 CODE DEFINITIONS, AN INCREASE IN CONDITIONED FLOOR AREA
 IS CONSIDERED AN ADDITION AND SHALL MEET THE
 REQUIREMENTS FOR NEW CONSTRUCTION IN ACCORDANCE WITH
 FBC-B 13-101.1.2. ADDITIONS TO EXISTING BUILDINGS SHALL
 FOLLOW THE SAME METHOD A CALCULATION PROCEDURE AS NEW
 CONSTRUCTION IN ACCORDANCE WITH FBC-B 13-400.2.A.1. ALL
 BUILDING ENVELOPE COMPONENTS FOR THE AREA OF THE
 ADDITION SHALL BE INCLUDED IN THE ENERGY CALCULATIONS.
  
 5. THE METHOD B FORM SUBMITTED SHOWS THE EQUIPMENT SIZE
 AS 12,300 BTU/H. THIS DOES NOT CORRESPOND WITH THE
 EQUIPMENT SHOWN ON THE PLANS OR THE COOLING LOAD
 CALCULATIONS. ALSO, ALL BUILDING ENVELOPE COMPONENTS
 ARE SHOWSN AS "EXISTING." WHILE THE PLANS SHOW MANY NEW
 ENVELOPE COMPONENTS BEING INSTALLED OR RETROFITTED. THE
 PLANS AND SPECIFICATIONS, INCLUDING THE ENERGY CODE
 CALCULATIONS, SHALL SHOW, IN SUFFICIENT DETAIL, ALL
 PERTINENT DATA AND FEATURES OF THE BUILDING AND THE
 EQUIPMENT AND SYSTEMS IN ACCORDANCE WITH FBC-B
 13-103.2.
  