| 2009-11-23 09:05:27 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. MOTORIZED DAMPER WITH SHUTOFF DAMPER CONTROLS IS |
| | REQUIRED ON THE OUTSIDE AIR INTAHE IN ACCORDANCE WITH |
| | FBC-B 13-409.AB.3.3. |
| | |
| | 2. A TYPE 2 HOOD IS REQUIRED OVER THE OVEN IN |
| | ACCORDANCE WITH FBC-M 507.2.2. THIS HOOD SHOULD MAY BE |
| | COVERED UNDER A SEPARATE PERMIT IN CONJUNCTION WITH THE |
| | TYPE 1 HOOD. |
| | |
| | 3. PRODUCT APPROVAL IS REQUIRED FOR ROOFTOP |
| | PRE-ENGINEERED A/C STAND IN ACCORDANCE WITH FBC-B |
| | 106.3.3 AND FAC RULE 9B-72. IF THE PROPOSED STAND IS |
| | FOR WALK-IN REMOTE CONDENSERS, THE PRODUCT APPROVAL MAY |
| | BE SUBMITTED WITH THE SEPARATE PERMIT APPLICATION FOR |
| | THE WALK-IN COOLERS. |
| | |
| | NOTE: NEW ROOFTOP CONDENSERS SHALL MEET THE |
| | REQUIREMENTS FOR GUARDS IF WITHIN 10' OF THE ROOF EDGE |
| | PER FBC-M 304.10 AND FOR SERVICE ACCESS IN ACCORDANCE |
| | WITH FBC-M 306.5. |
| | |
| | ENERGY CALCULATIONS: |
| | |
| | 4. A LARGE PORTION OF THIS BUILDING IS BEING CONVERTED |
| | FROM UNCONDITIONED TO CONDITIONED SPACE. PER ENERGY |
| | CODE DEFINITIONS, AN INCREASE IN CONDITIONED FLOOR AREA |
| | IS CONSIDERED AN ADDITION AND SHALL MEET THE |
| | REQUIREMENTS FOR NEW CONSTRUCTION IN ACCORDANCE WITH |
| | FBC-B 13-101.1.2. ADDITIONS TO EXISTING BUILDINGS SHALL |
| | FOLLOW THE SAME METHOD A CALCULATION PROCEDURE AS NEW |
| | CONSTRUCTION IN ACCORDANCE WITH FBC-B 13-400.2.A.1. ALL |
| | BUILDING ENVELOPE COMPONENTS FOR THE AREA OF THE |
| | ADDITION SHALL BE INCLUDED IN THE ENERGY CALCULATIONS. |
| | |
| | 5. THE METHOD B FORM SUBMITTED SHOWS THE EQUIPMENT SIZE |
| | AS 12,300 BTU/H. THIS DOES NOT CORRESPOND WITH THE |
| | EQUIPMENT SHOWN ON THE PLANS OR THE COOLING LOAD |
| | CALCULATIONS. ALSO, ALL BUILDING ENVELOPE COMPONENTS |
| | ARE SHOWSN AS "EXISTING." WHILE THE PLANS SHOW MANY NEW |
| | ENVELOPE COMPONENTS BEING INSTALLED OR RETROFITTED. THE |
| | PLANS AND SPECIFICATIONS, INCLUDING THE ENERGY CODE |
| | CALCULATIONS, SHALL SHOW, IN SUFFICIENT DETAIL, ALL |
| | PERTINENT DATA AND FEATURES OF THE BUILDING AND THE |
| | EQUIPMENT AND SYSTEMS IN ACCORDANCE WITH FBC-B |
| | 13-103.2. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |
| | RONALD J. REGUEIRO |
| | 561.805.6719 |
| | [email protected] |