| Plan Review Notes For Permit 09110018 |
| Permit Number |
09110018 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-11-05 07:32:24 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 | | | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING | | | | | | ALL COMMENTS RELATE TO SHEET E-6 | | | | | | 1} REVISION REQUIRED FOR GEC PER 250.50, 250.52 & | | | 250.66. SHEET E-6 ONLY NEEDS REVISED. | | | | | | 2} NOTE THAT THE TRANSFER SWITCH WILL BE MANUAL, SUBMIT | | | MANUFACTURERS SPECIFICATIONS FOR SAME. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|