Plan Review Notes
Plan Review Notes For Permit 09110018
Permit Number 09110018
Review Stop E
Sequence Number 1
Notes
Date Text
2009-11-05 07:32:24 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 ALL COMMENTS RELATE TO SHEET E-6
  
 1} REVISION REQUIRED FOR GEC PER 250.50, 250.52 &
 250.66. SHEET E-6 ONLY NEEDS REVISED.
  
 2} NOTE THAT THE TRANSFER SWITCH WILL BE MANUAL, SUBMIT
 MANUFACTURERS SPECIFICATIONS FOR SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  