| 2009-11-05 07:26:51 | | | | | | | | | | PASSED/PROVISO: | | | SHT A-703 DETAIL 6, SHOW COMPLIANCE FOR THE FOLLOWING: | | | A. 11-4.24.3 KNEE CLEARANCE | | | B. 11-4.24.4 SINK DEPTH | | | C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH | | | REQUIRED, CABINET DOORS PROHIBITED) | | | D. 11-4.24.6 EXPOSED PIPES & SURFACES. | | | (REVISION REQUIRED) (SUBMIT ELEVATION FOR SINK) | | | | | | SHT P-501 ELECTRIC WATER HEATER 2 + 3 DETAIL REFERENCES | | | DETAIL 4/P6.02. SHEET P6.02 HAS NOT BEEN SUBMITTED IN | | | PLANS. REVISION REQUIRED CHANGING DETAIL ON SHT P-501 | | | OR SHEET P6.02 SHALL BE SUBMITTED AS A REVISION SHOWING | | | DETAIL REFERENCED. SECTIONS 504.6 & 504.7.2. | | | | | | | | | | | | | | | | | | . |
|