2009-11-23 13:54:51** DENIED **
  
 1) NOTE: PLANS ARE SUBMITTED FOR PERMIT APPLICATION
 AFTER OCTOBER 1ST, 2009. THIS PLACES THE DESIGN TO BE
 UNDER THE 2008 NEC. PLANS STATE ON SHEET LS101 STATE
 DESIGN UNDER 2005.
 ELECTRICAL SHEET E001 STATES THE CORRECT ELECTRICAL
 CODE HOWEVER NOT THE CORRECT LIFE SAFETY CODE. PLANS
 STATE 2003 HOWEVER PER FLORIDA ADMINISTRATIVE CODE
 69A-60.003,.004, 69A-3.012 AS OF DECEMBER 31ST, 2008
 THE ADOPTED NFPA-101 IS THE 2006 EDITION. PLEASE
 ADJUST.
 PLEASE SEE SHEET E-401 WHICH UNDER GENERAL NOTES #3
 STATES THE 2009 NEC. THERE IS NO 2009 NEC.
  
 2) NOTE: THE SUBMITTED FLA COM ENERGY CALCULATIONS ARE
 METHOD *A* FOR WHOLE BUILDING COMPLIANCE. THIS IS AN
 EXISTING BUILDING, PLEASE EXPLAIN USE OF METHOD *A*.
 PLEASE ALSO KNOW THAT NEW CONSTRUCTION AND USING METHOD
 *A* WOULD MEANT THAT EVERY COMPONENT OF THE BUILDING
 CONSTRUCTION INCLUDING ENERGY USE AND ITEMS WHICH
 AFFECT ENERGY USE MUST BE INCLUDED. THE INPUT DATA
 REPORT IS REQUIRED TO BE COMPLETE WITH ALL CONSTRUCTION
 ASPECTS OF THE BUILDING.
 13-101.1,13.101.1.3, 13-101.4.1, 13-400.0.A,
 13-400.0.B, 13-400.0.B.4
  
 PLEASE SEE SPECIFICALLY EXTERIOR LIGHTING WHICH IS
 COMPLETELY BLANK ON THE SUBMITTED CALCULATIONS AND
 INPUT DATA REPORT.
 THERE IS A SUBSTANTIAL AMOUNT OF PARKING LOT LIGHTING
 WHICH IS FED FROM THIS BUILDING ELECTRICAL SERVICE.
 PLEASE SEE SECTION 13-415.AB.2. SEE TABLE
 13-415.AB.2.2.
 PLEASE ALSO SEE OTHER COMPONENTS SUCH AS DOORS (SECTION
 13-403) WHICH ARE BLANK, ALONG WITH PIPING (SECTION
 13-411, 13-412 ETC.
 IF METHOD *A* IS GOING TO BE USED AS THIS WERE NEW
 CONSTRUCTION, ALL MUST BE COMPLETED.
 DISPLAY OR ACCENT LIGHTING IN THE IDR MAY NOT BE USED
 AS NONE OF THIS LIGHTING IN THIS OCCUPANCY MEETS THE
 EXEMPTIONS OF THE LIGHTING PERFORMANCE CALCULATION
 PROCEDURES. SPACES ARE 121, 191, 101B.
 ANOTHER AREA WOULD BE TWO OF THE EXISTING RESTROOMS.
 THEY CAN NOT BE EXISTING AND NOT BE PLACED INTO THE IDR
 AS SPACES FOR METHOD *A*.
 PLANS INDICATE WHAT APPEARS TO BE METHOD B SPACE BY
 SPACE. MAY NOT USE BOTH VERSIONS/METHODS. 13-415.AB.5
 THERE WERE SUBSTANTIAL CHANGES TO THE 2007 FBC W/ 2009
 SUPPLEMENTS. THERE ARE NO LONGER ALLOWANCES FOR THIS
 SPACE.
  
 3) NOTE: PLEASE EXPLAIN SOME OF THE LIGHTING CONTROLS.
 BASED ON THE SYMBOL LEGEND MANY OF THESE DEVICES ARE
 STANDARD SINGLE POLE OR THREE POLE DEVICES. MANY OF THE
 LIGHTS HAVE AREA OCCUPANCY SENSORS HOWEVER NOT ALL.
 FOR EXAMPLE: PLEASE SEE THE FRONT ENTRY AREA WHICH
 INDICATE A8 TYPE FIXTURES ON PANEL LP-1, CIRCUIT 13.
 THESE ARE SHOWN BEING CONTROL BY A SINGLE POLE SWITCH
 WITH NO AUTOMATED CONTROLS AS REQUIRED PER
 13-415.AB.1.1,.1.2, .1.3.
  
 4) NOTE: PLEASE INDICATE NEW OR EXISTING ROOF TOP GFI
 REQUIRED FOR A/C EQUIPMENT. 210.63, 210.8B3
  
 5) NOTE: HOW ARE THE LIGHTS IN STAIRS CONTROLLED?
 NOTED: PLEASE SEE FBC 1006.1.2 AND NFPA-101 7.8.1.2.2
 FOR TYPES OF OCCUPANCY SENSORS REQUIRED WHEN USING FOR
 CONTROL OF EGRESS LIGHTING. THIS IS FOR ALL EGRESS
 PATHS NOT ONLY STAIRS.
 ( DEVICES SHALL FAIL SAFE *ON*) KEY NOTES ON PLANS
 ALREADY INDICATE THIS ON E201 HOWEVER IS NOTED FOR
 CLARITY AS CONTROLS FOR STAIR LIGHTING IS NOT SHOWN.
  
 6) NOTE: PLEASE INDICATE THE PHOTO-METRIC LEVELS FOR
 STAIRS UNDER NORMAL AND EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.1.2, .2.2.
 10FT CANDLES REQUIRED UNDER NORMAL AND 1FT CANDLE IS
 PERMITTED UNDER EMERGENCY FOR STAIRS. ALL OTHER LEVEL
 EGRESS WALKING SURFACES ARE 1FT CANDLE WHICH BASED ON
 PLANS AND LIGHTING SHOWN APPEARS TO BE MET.
  
 7) NOTE: PLANS INDICATE RELOCATION OF TIME CLOCK FOR
 EXTERIOR LIGHTING HOWEVER LIGHTING CONTROLS MUST MEET
 PRESCRIPTIVE FOR NEW INSTALLED. DOES TIME CLOCK MEET
 13-415.AB.1.4 FOR EXTERIOR CONTROLS?
  
 8) NOTE: PLEASE TAKE A LOOK AT THE LOAD CALCULATIONS ON
 SHEET E501. THE CODE SECTIONS LISTED ARE NOT FROM
 CURRENT 2008 NEC OR FROM THE 2005 NEC.
 ONE SECTION IS NOTED AS 220.21 WHICH IS NOT PART OF
 CODES LISTED. PLEASE ALSO SEE 220.14 AS NOTED.
 PLEASE ALSO SEE THAT THE LOAD CALCULATIONS ARE NOT
 LISTING ANY LIGHTING LOADS. HOW IS THIS POSSIBLE WHEN
 THE LP CONTAINS NUMEROUS LIGHTING CIRCUITS?
 THE LIGHTING COLUMN ACTUALLY INDICATES 0.00 LOAD WITH A
 DEMAND OF 125% AND DEMAND LOAD OF 0.00. PLEASE EXPLAIN
 AS THE LOAD OF 17.9 ON THE LP PANEL APPEARS TO BE UNDER
 THE RECEPTACLE COLUMN LOAD.. PLEASE SEE 220.42,220.12,
 230.42, 215.5 ETC.
  
 9) NOTE: PLEASE SEE NEC 517 PART II, BEGINNING WITH
 517.13 AND ADJUST PLANS. PLEASE SEE THE FOLLOWING WHICH
 IS EXTRACTED FORM THE NEC COMMENTARY UNDER 517.1.
 ***
 THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY
 TO ALL TYPES OF HEALTH CARE FACILITIES. THE
 REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE
 NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC
 MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES
 WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE
 WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE
 REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER
 PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS
 ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE
 REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45
 IN ARTICLE 517.**
  
  
 10) NOTE: PLEASE SEE 2008 NEC 210.8B5 AS *ALL*
 RECEPTACLES IN AREAS LISTED ARE REQUIRED TO BE GFI/GFI
 PROTECTED. THIS IS REQUIRED WHETHER OR NOT THEY ARE
 DEDICATED CIRCUITS SUCH AS THE REFRIGERATOR. THE 2005
 NEC HAD SUBSTANTIAL CHANGES TO 210.8 FOR RESIDENTIAL
 AND THE 2008 NEC HAS EXPANDED GFI PROTECTION.
  
 11) NOTE: PLEASE LIST AIC RATING FOR NEW SERVICE
 ENTRANCE RATED DISCONNECT. 110.9
  
 12) NOTE: PLEASE INDICATE THE FEEDERS AND CONDUITS FROM
 THE SERVICE MAIN TO THE MDP. THE RISER ONLY INDICATES
 SEC AHEAD OF THE MAIN.
 310.16, 240.4, ETC
 PLEASE BE SURE TO ALSO INCLUDE THE REQUIRED EQUIPMENT
 GROUNDING CONDUCTOR(S) SIZED PER 250.122.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  