2009-11-03 17:58:31BUILDING PLAN REVIEW
 PERMIT: 09100591
 ADD: 1552 PALM BEACH LAKES BLVD
 CONT: NCY CONSTRUCTION INC
 TEL: (561)543-3457
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES
 IN THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) SHEET A-501 THE NORTH ELEVATION INDICATES THE RE-USE
 OF EXISTING ALUMINUM STOREFRONT FRAMES AND NEW 9/16"
 CLEAR IMPACT GLAZING BEING INSTALLED INTO THE FRAMES.
 PLEASE EITHER PROVIDE EITHER ENGINEERING AND OR
 RATIONAL ANALYSIS FOR THE INSTALLATION OF GLAZING INTO
 THE FRAME AND INSTALLATION OF WINDOW ASSEMBLY TO THE
 NEW OPENING WITHIN THE STRUCTURE.
  
 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 2) SHEET S1.0 WIND DESIGN CRITERIA, THE PLANS INDICATE
 A EXPOSURE CATEGORY TYPE "B" PLEASE REVIEW1609.4.3.
 EXPOSURE C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS,
 INCLUDING SURFACE UNDULATIONS OR OTHER IRREGULARITIES,
 HAVING HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM)
 EXTENDING MORE THAN 1,500 FEET (457.2 M) FROM THE
 BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO
 APPLY TO ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF EXPOSURE
 C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND
 DIRECTION.
  
 THE C-TYPE TERRAIN WILL CAUSE THE PRESSURES TO BE
 HIGHER ON THE NEW OPENINGS WITH HIGHER POSITIVE AND
 NEGATIVE PRESSURES, PLEASE UPDATE PLANS.
  