| 2009-11-03 17:58:31 | BUILDING PLAN REVIEW |
| | PERMIT: 09100591 |
| | ADD: 1552 PALM BEACH LAKES BLVD |
| | CONT: NCY CONSTRUCTION INC |
| | TEL: (561)543-3457 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES |
| | IN THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) SHEET A-501 THE NORTH ELEVATION INDICATES THE RE-USE |
| | OF EXISTING ALUMINUM STOREFRONT FRAMES AND NEW 9/16" |
| | CLEAR IMPACT GLAZING BEING INSTALLED INTO THE FRAMES. |
| | PLEASE EITHER PROVIDE EITHER ENGINEERING AND OR |
| | RATIONAL ANALYSIS FOR THE INSTALLATION OF GLAZING INTO |
| | THE FRAME AND INSTALLATION OF WINDOW ASSEMBLY TO THE |
| | NEW OPENING WITHIN THE STRUCTURE. |
| | |
| | 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | 2) SHEET S1.0 WIND DESIGN CRITERIA, THE PLANS INDICATE |
| | A EXPOSURE CATEGORY TYPE "B" PLEASE REVIEW1609.4.3. |
| | EXPOSURE C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS, |
| | INCLUDING SURFACE UNDULATIONS OR OTHER IRREGULARITIES, |
| | HAVING HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM) |
| | EXTENDING MORE THAN 1,500 FEET (457.2 M) FROM THE |
| | BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO |
| | APPLY TO ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE |
| | TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET |
| | HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF EXPOSURE |
| | C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9 |
| | M) AND WIDTH GREATER THAN 150 FT. IN THE UPWIND |
| | DIRECTION. |
| | |
| | THE C-TYPE TERRAIN WILL CAUSE THE PRESSURES TO BE |
| | HIGHER ON THE NEW OPENINGS WITH HIGHER POSITIVE AND |
| | NEGATIVE PRESSURES, PLEASE UPDATE PLANS. |
| | |