| 2009-11-24 08:05:35 | ** DENIED ** |
| | |
| | 1) NOTE: PLANS ARE SUBMITTED FOR PERMIT APPLICATION |
| | AFTER OCTOBER 1ST, 2009. THIS PLACES THE DESIGN TO BE |
| | UNDER THE 2008 NEC. SEVERAL CODE SECTIONS REFLECTED ON |
| | DESIGN DOCUMENTS ARE NOT FROM THE 2008 NEC OR THE 2005 |
| | NEC. |
| | PLEASE ADJUST NOTES FOR CORRECT CODES. |
| | PLEASE ALSO KNOW THE CODE IN WHICH THE PROJECT IS |
| | DESIGNED SHALL BE LISTED ON PLANS. |
| | |
| | 2) NOTE: THE VALUE FOR THE COMPLETE SCOPE OF WORK IS |
| | LOW. THE VALUE IS REQUIRED TO INCLUDE ALL LABOR, |
| | EQUIPMENT, EQUIPMENT SUPPLIED BY OWNER, MATERIALS, |
| | CONTRACTOR OVER HEAD, CONTRACTOR PROFIT, COST OF PLAN |
| | DESIGN ETC. EVEN IF ANY OF THESE ARE OWNER SUPPLIED. |
| | FBC 108.3 AS ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | THE PROPOSED EQUIPMENT AS SHOWN ON PLANS ALONG WITH |
| | MATERIALS IS SUBSTANTIALLY HIGHER THAN THE COMPLETE |
| | APPLIED VALUE OF $10K. |
| | PLEASE ADJUST OR ONE WILL BE ASSESSED USING ADOPTED |
| | GUIDES. |
| | |
| | 3) NOTE: THE PROPOSED TRANSFORMER SHOWN ON PLANS AT |
| | GARAGE IS IN THE WORKING CLEARANCE OF THE METER PER |
| | 110.26. |
| | |
| | 4) NOTE: PLEASE SHOWN ALL DISCONNECTING MEANS AT |
| | DETACHED BUILDING PER 225.31-225.39. |
| | |
| | 5) NOTE: PLEASE INDICATE GROUNDING PER 250.32,250.50 |
| | FOR DETACHED BUILDING. |
| | |
| | 6) NOTE: RISER DOES NOT INDICATE ANY EQUIPMENT |
| | GROUNDING CONDUCTOR FROM GENERATOR PLUG. PLEASE SEE |
| | 250.122 FOR SIZING. |
| | |
| | 7) NOTE: PLEASE INDICATE GROUNDING OF SEPARATELY |
| | DERIVED SYSTEMS PER 250.30.250.20 |
| | |
| | 8) NOTE: PLEASE SEE 250.94 FOR INTERSYSTEM BONDING |
| | TERMINATION. |
| | |
| | 9) NOTE: PLEASE SEE 250.50 AND OTHER GROUNDING SECTIONS |
| | NOTED ABOVE. THE RISER INDICATES 1-#8 FOR GROUNDING |
| | ELECTRODE CONDUCTOR HOWEVER NO ATTACHMENT LOCATION IS |
| | SHOWN. |
| | 250.50,250.53,250.56, 54 ETC |
| | |
| | 10) NOTE: GROUNDING ELECTRODE CONDUCTOR IS REQUIRED TO |
| | BE SIZED PER 250.66. THE #8 SHOWN IS TOO SMALL. |
| | |
| | 11) NOTE: PLEASE INCLUDE VOLTAGE DROP CALCULATIONS PER |
| | FBC 13-413.AB.1 |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |