| 2009-11-06 10:53:43 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M1 SHOWS SUPPLY AND EXHAUST DUCTS PENETRATING | | | 1-HOUR RATED WALL. SEE WALL TYPE "B" AS SHOWN ON PAGE | | | A3.0. SHOW HOW THESE PENETRATIONS ARE TO BE PROTECTED | | | IN ACCORDANCE WITH FBC-M 607.5 AND 607.8. | | | | | | 2. THE FULL-HEIGHT FIRE RESISTANCE RATED WALL WILL | | | PROHIBIT THE FLOW OF RETURN AIR THROUGH THE PLENUM | | | CEILING BACK TO THE AIR HANDLING EQUIPMENT. PROVIDE | | | TRANSFER AIR OPENINGS IN THE RATED WALL TO FACILITATE | | | BALANCED RETURN IN ACCORDANCE WITH FBC-M 601.4. ALSO, | | | SHOW HOW THESE TRANSFER OPENINGS ARE TO BE PROTECTED IN | | | ACCORDANCE WITH FBC-M 607.5 AND 607.8. | | | | | | 3. PAGE M1 SHOWS CEILING EXHAUST FANS WITH POSITIVE | | | PRESSURE EXHAUST DUCTS WITHIN THE PLENUM CEILING. | | | EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL NOT EXTEND | | | INTO OR PASS THROUGH PLENUMS IN ACCORDANCE WITH FBC-M | | | 601.5. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|