| 2009-11-17 12:05:40 | 2007 FBC W/2009 REVISIONS | | | STORM PANELS | | | | | | DENIED | | | | | | 1) DIRECT MOUNT IS SPECIFIED FOR SOME OF THE STORM | | | PANEL CONNECTION TYPES AND THE ONLY ANCHORS THAT ARE | | | SPECIFIED ARE TAPCONS. TAPCONS ARE NOT ACCEPTABLE FOR | | | DIRECT MOUNT PER PRODUCT APPROVAL. | | | | | | 2) TABLE 2 NOTE ON PAGE 6 OF THE PRODUCT APPROVAL | | | SPECIFIES A MINIMUM PANEL LENGTH FOR THE VARIOUS | | | MOUNTING CONDITIONS. THE TABLE STATES THAT PANEL | | | LENGTHS LESS THAN THOSE NOTED IN THE TABLE REQUIRE SITE | | | SPECIFIC POROSITY CALCULATIONS BY A PROFESSIONAL | | | ENGINEER. SOME OF THE PANEL LENGTHS ARE LESS THAN THE | | | MINIMUMS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|