| Plan Review Notes For Permit 09100489 |
| Permit Number |
09100489 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-11-02 12:30:43 | 2007 FBC W/2009 REVISIONS | | | STORM PANELS | | | | | | DENIED BY BUILDING | | | | | | 1) THE COMPONENT AND CLADDING PRESSURES FOR THE | | | OPENINGS TO BE SHUTTERED ARE TOO LOW. PLEASE REVISE. | | | FBC R301.2(2) | | | | | | 2) THE ANCHOR SPACING FOR OPENING NUMBERS 5, 8 AND 11 | | | ARE INCORRECT FOR CORRECTED PRESSURES. | | | | | | 3) THE ANCHOR TYPE ON THE SCHEDULE FOR THE ALUMINUM | | | STORM PANELS IS SPECIFIED AS TAP CONS, HOWEVER ON THE | | | PRODUCT APPROVAL THE ELCO PANEL MATES ARE SELECTED. | | | PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|