Plan Review Notes For Permit 09100440
Permit Number 09100440
Review Stop P
Sequence Number 3
Notes
Date Text
2010-01-27 08:57:35 
  
  
 PASSED/PROVISO:
  
 REVISION REQUIRED...
  
 SHT P-1 A RELIEF VENT IS REQUIRED FOR THE AAV'S.
 SECTION 917.3.2.
  
 917.3.2 RELIEF VENT. WHERE THE HORIZONTAL BRANCH IS
 LOCATED MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF
 THE STACK, THE HORIZONTAL BRANCH SHALL BE PROVIDED WITH
 A RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR
 STACK VENT, OR EXTEND OUTDOORS TO THE OPEN AIR. THE
 RELIEF VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 DRAIN BETWEEN THE STACK AND THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTED TO THE HORIZONTAL BRANCH DRAIN. THE
 RELIEF VENT SHALL BE SIZED IN ACCORDANCE WITH SECTION
 916.2 AND INSTALLED IN ACCORDANCE WITH SECTION 905. THE
 RELIEF VENT SHALL BE PERMITTED TO SERVE AS THE VENT FOR
 OTHER FIXTURES.