Plan Review Notes
Plan Review Notes For Permit 09100440
Permit Number 09100440
Review Stop P
Sequence Number 2
Notes
Date Text
2009-12-22 08:49:35DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 EXISTING BUILDING
 FBC-2007 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. PLEASE DECLARE THE OCCUPANCY AS REQUIRED IN SECTION
 106.3.5.1.1(2).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE
 OCCUPANCY OR USE OF THE TENANT SPACE IS REQUIRED, NOT
 THE OCCUPANCY LOAD.
  
 2. OK
 3. OK
  
 4. SHT P-1 A RELIEF VENT IS REQUIRED FOR THE AAV'S.
 SECTION 917.3.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PER
 SECTION 917.3.2:
 917.3.2 RELIEF VENT. WHERE THE HORIZONTAL BRANCH IS
 LOCATED MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF
 THE STACK, THE HORIZONTAL BRANCH SHALL BE PROVIDED WITH
 A RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR
 STACK VENT, OR EXTEND OUTDOORS TO THE OPEN AIR. THE
 RELIEF VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 DRAIN BETWEEN THE STACK AND THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTED TO THE HORIZONTAL BRANCH DRAIN. THE
 RELIEF VENT SHALL BE SIZED IN ACCORDANCE WITH SECTION
 916.2 AND INSTALLED IN ACCORDANCE WITH SECTION 905. THE
 RELIEF VENT SHALL BE PERMITTED TO SERVE AS THE VENT FOR
 OTHER FIXTURES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  