Plan Review Notes
Plan Review Notes For Permit 09100440
Permit Number 09100440
Review Stop E
Sequence Number 2
Notes
Date Text
2009-12-22 13:18:15 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE
 PREVIOUS REVIEW.
  
 4} FBC 13-415.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED
 BY CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE
 CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL
 LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE SHALL BE
 READILY ACCESSIBLE AND LOCATED SO THE OCCUPANTS CAN SEE
 THE CONTROLLED LIGHTING
  
 5} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1 THIS CAN BE DEMONSTRATED ON THE PLANS
 INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN FOR
 THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
 INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE
 WITH THE ONES IN THE CALCULATIONS.
  
 NOTE : THE FIXTURE SCHEDULE ON SHEET E-1 DOES NOT
 CORRELATE WITH THE SCHEDULE ON SHEET A-2.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  